The generator can be perfect, the engine can be perfect, and the installation can still fail — because of the cable. Enter your generator's kVA (or kW and power factor), the voltage and phase, and the one-way run length, and the tool returns the load current, the minimum conductor by ampacity, the minimum conductor by voltage drop, and the final size in AWG and mm² — with the percentage voltage drop for each option.

Ampacity & voltage drop
AWG & mm² sizing
Single & three‑phase
Calculate Cable Size
Free cable sizing tool for generator installations.
ShanHua Power

Cable Sizing Reference

Proper cable sizing prevents voltage drop, overheating, and failed motor starts.

25+ Years experience
8–4,000 kVA generator range
20+ Countries supplied
Cable Sizing

Voltage Drop vs Voltage Dip: Two Different Problems

Voltage drop is the steady loss of voltage along a cable, caused by conductor resistance. Voltage dip is the brief sag in a generator's output the moment a large motor starts, caused by the alternator's reactance. They are easy to confuse — and often happen at the same time.

Voltage Drop Steady Cable Loss

The steady loss of voltage along a cable, caused by conductor resistance (V = I × R). It is constant while the load runs and you fix it by using a larger cable.

Voltage Dip Generator Sag

The brief sag in a generator's output the moment a large motor starts, caused by the alternator's reactance. It lasts only a second or two and you fix it by choosing a generator with enough starting kVA.

They Add Together At the Load

When a motor starts, the surge produces both a dip at the generator and extra drop in the cable. A motor that is fine on a short, thick feeder can stall on a long, thin one — because the cable is too small.

Two Halves of One Installation

This page is about voltage drop — the steady loss in the cable. The voltage dip side of the problem is handled by our companion motor starting generator sizing calculator, which sizes for the starting kVA. Size the cable here, check the motor start there, and you have both halves of the installation covered.

Key Differences

Voltage Drop vs Voltage Dip

01
Drop = Cable Loss

Voltage drop is steady, caused by cable resistance, and fixed by a larger conductor. It affects the load continuously while it runs.

02
Dip = Generator Sag

Voltage dip is brief, caused by alternator reactance, and fixed by generator starting kVA. It only occurs during the first second of motor startup.

03
They Add at Startup

When a motor starts, the dip and the extra drop happen together. The load sees the sum of both — which is why a long cable can cause a motor to stall.

04
Two Tools, One Solution

Size the cable here using the voltage drop calculator. Check the motor start using the motor starting generator sizing calculator. Together they cover the whole installation.

Cable Sizing Tool

How the Generator Cable Size Calculator Works

A generator feeder must satisfy two independent constraints, and the final conductor is whichever is larger. Choose Quick Mode for a fast estimate based on generator kVA, or Advanced Mode for detailed calculations with conductor material, temperature, and NEC derating factors.

Fast Cable Sizing Estimate

Enter generator kVA and run length. The tool returns load current, ampacity-based size, voltage-drop-based size, and the final conductor — with percentage voltage drop for each option.

Enter the generator's rated kVA
Line-to-line voltage (V)
Feet (ft)

Detailed Cable Sizing with Derating

Enter generator power, conductor details, installation conditions, and derating factors for a complete NEC-compliant cable sizing.

kVA
Feet (ft)
Feeder Sizing Reference

Generator Feeder Sizing Rules: NEC 445.13, 3% and 5%

Generator feeder sizing is governed by a few hard rules. NEC 445.13 requires conductors to have an ampacity of at least 115% of the generator's nameplate current rating. Voltage-drop limits follow common design practice: 3% for branch circuits, 5% combined for feeder and branch.

Rule / Standard Requirement Application
NEC 445.13 ≥ 115% nameplate current Generator feeder conductors
Branch circuit drop ≤ 3% Individual branch circuits
Feeder + branch combined ≤ 5% Total from generator to load
Generator to switchboard (marine) ≤ 1% Shipboard installations
Manual rule of thumb ≤ 5% General generator feeders
Motor starting allowance Extra margin Voltage sag stacks on cable drop
Key takeaway: A 100 A generator needs conductors sized for at least 115 A. If you size the cable right up to the 5% limit, a motor start can push the combined figure well past it. Always leave extra margin for generator output sag during motor starting.
Sizing Examples

What Size Wire for a Generator? Worked Examples

The table below shows the drop for real generator scenarios, calculated with the formulas above (copper, K = 12.9). Use it as a sense check before you run the calculator.

SCENARIO 01

22 kW Standby — 2 AWG

Voltage: 240 V, Single‑phase
Current: 91.7 A
Run: 220 ft
Conductor: 2 AWG Cu
Voltage drop: ≈ 3.3%

SCENARIO 02

22 kW Standby — 1/0 Cu

Voltage: 240 V, Single‑phase
Current: 91.7 A
Run: 220 ft
Conductor: 1/0 Cu
Voltage drop: ≈ 2.1%

SCENARIO 03

45 kW, Three‑Phase — 2 AWG

Voltage: 208 V, Three‑phase
Current: 125 A
Run: 160 ft
Conductor: 2 AWG Cu
Voltage drop: ≈ 3.2%

SCENARIO 04

45 kW, Three‑Phase — 1/0 Cu

Voltage: 208 V, Three‑phase
Current: 125 A
Run: 160 ft
Conductor: 1/0 Cu
Voltage drop: ≈ 2.0%

SCENARIO 05

Portable — 10 AWG vs 8 AWG

Voltage: 240 V, Single‑phase
Current: 30 A · Run: 85 ft
10 AWG Cu: ≈ 2.6% drop
8 AWG Cu: ≈ 1.7% drop
8 AWG gives cleaner margin

Three Lessons

What the Table Tells You

1. Distance drives the decision. At 160–220 ft, the difference between 2 AWG and 1/0 is the difference between borderline and comfortable — the voltage drop check, not the ampacity check, forces the upsize.

2. Motor loads push you bigger. The 22 kW and 45 kW sets run HVAC and pump motors; staying near 2% (1/0) rather than 3% (2 AWG) leaves starting margin.

3. Even small runs deserve a check. A 30 A portable generator at 85 ft is fine on 10 AWG, but 8 AWG gives a cleaner margin if a compressor or pump is on the circuit.

Material & Phase

Copper vs Aluminum & Three‑Phase Generator Feeders

Two choices recur on every generator installation: the conductor material and the phase arrangement — and each changes the calculation. The calculator reports both so you can weigh the upsize against the material cost.

01

Copper Conductors

Copper carries more current per cross‑section and drops less voltage for a given size. It costs more and weighs more than aluminum. For a short, tightly packed terminal box, copper usually wins.

02

Aluminum Conductors

Aluminum is lighter and cheaper than copper, but you need a larger conductor for the same ampacity and voltage drop — its resistivity is 0.0282 Ω·mm²/m versus copper's 0.0175. For a long outdoor feeder, the aluminum upsize is often the economical choice.

03

Three‑Phase Feeders

A three‑phase generator is three single‑phase circuits sharing one engine. The current formula changes accordingly (÷ 1.732). The terminal box, busbar, and recommended feeder are engineered together.

04

Power Factor in Three‑Phase

A motor‑heavy load with a power factor below 0.8 draws more apparent power than its kilowatts suggest, which raises the current — and the voltage drop — for the same run. The calculator's three‑phase mode takes your power factor and reflects it in the result.

05

Resistivity Constants

Exact results shift slightly with the resistivity constant you use — 12.9 is standard for larger conductors, while finer conductors run closer to 10.8. Treat every figure here as a planning value, not a spec. The calculator uses 12.9 for copper and 21.2 for aluminum.

06

Huali Terminal Integration

For a Huali three‑phase set, the terminal box, busbar, and recommended feeder are engineered together. The cable size you calculate here is the one our engineers will specify on the nameplate drawing.

Common Errors

Common Generator Cable Sizing Mistakes

Most cable sizing problems come from a small number of recurring assumptions. Avoiding these errors helps prevent both undersized conductors and unnecessary excess cost.

01

Sizing Only for Ampacity

A conductor that meets the ampacity requirement can still drop too much voltage over a long run. The final size is always the larger of ampacity and voltage drop — never assume ampacity alone is enough.

02

Forgetting Motor Starting Margin

The generator's output sags during motor starting, and that sag stacks on top of the cable drop. If you size the cable right up to the 5% limit, a motor start can push the combined figure well past it.

03

Ignoring Power Factor in Three‑Phase

A motor‑heavy load at 0.7 PF draws more current than the same kW at 0.9 PF — which means higher voltage drop. Always enter the actual power factor of your load, not the generator's default.

04

Treating Copper and Aluminum Interchangeably

Aluminum has higher resistivity — you need a larger conductor for the same ampacity and voltage drop. The calculator reports the answer in both materials so you can weigh the upsize against the material cost.

05

Using the Wrong Voltage Drop Constant

The K value changes with conductor size and temperature. 12.9 is standard for larger copper conductors; finer conductors run closer to 10.8. The calculator uses 12.9 for copper and 21.2 for aluminum — consistent with standard feeder design.

Final generator cable sizing should always check both ampacity (NEC 445.13 — 115% of nameplate current) and voltage drop. Use the cable size calculator to run both checks automatically, and confirm the final conductor with your project's local code requirements.