Commercial Electrical Load Calculator

Commercial Electrical Load kW, kVA & Generator for Your Building

Guess at your commercial load and you'll pay twice: once in a service that can't carry the building, and once in a generator that trips when the AC and compressors start together. Our free calculator returns demand load in kVA, service size in amps, and a diesel generator recommendation — based on NEC Article 220. Built by Shandong Huali, a diesel generator manufacturer since 1999, with models from 8–4,000 kVA. Get a factory-direct quote with your results pre-filled.

Demand load in kVA & kW
Service size in amps
Standby & prime generator sizing
Calculate My Building's Load
Free tool – get your kVA, amps, and a diesel quote.
Shandong Huali

Diesel Generator Manufacturer

Factory-direct commercial power since 1999.

25+ Years experience
8–4,000 kVA generator range
20+ Countries supplied
Commercial Load Basics

What a Commercial Electrical Load Calculator Does

A commercial electrical load calculator works out how much electrical demand a business property really draws, in volt-amperes (VA), kilowatts (kW), and kilovolt-amperes (kVA). It applies the demand factors of the National Electrical Code (NEC) to the building's lights, outlets, HVAC, motors, and equipment, and returns the number every downstream decision hangs on.

VA Volt-Amperes

The code calculates in volt-amperes, not watts. Mixing watts into a motor or transformer load undersizes your conductors.

kW Real Power

The actual usable power your equipment consumes. Generators are rated in kVA at a 0.8 power factor, so the translation is direct.

kVA Apparent Power

The total capacity your generator must provide. Demand load in kVA is the starting point for backup power sizing.

From Connected Load to Demand Load

The difference between connected load and demand load is the whole game. Connected load is every watt of everything installed. Demand load is what the building actually draws at its peak, after demand factors, because nothing runs at full capacity at the same time. Code-based demand factors turn the first into the second, and that's the number that sizes your service and your generator.

Answers Four Key Questions

What the Calculator Tells You

01
Total Electrical Demand

What is my building's total electrical demand? The calculator returns the real number in VA, kW, and kVA — not a guess.

02
Service Size in Amps

What service size in amps do I need? The calculator divides demand VA by your system voltage to give you the next standard service size.

03
Generator Size

What size generator do I need for standby or prime power? The calculator returns both recommendations mapped to real models.

04
Operating Cost

What will that generator cost to run? The calculator shows estimated fuel cost per hour, linked to the fuel consumption tool.

Commercial Electrical Load Calculator
Commercial Load Tool

Commercial Electrical Load Calculator

Enter your building type, square footage, voltage, and equipment. The calculator applies NEC Article 220 demand factors and returns your demand load in kVA, service size in amps, and a diesel generator recommendation.

Building & Equipment Details

Select your building type and fill in the values. Equipment defaults are pre-loaded for each occupancy.

Equipment Loads (VA)

Edit values to match your building. Lighting is auto-calculated from square footage.

Load Chart & NEC Rules

Commercial Electrical Load Chart by Building Type

The chart below is a planning reference. The lighting figures are the NEC minimum unit loads for service sizing, and the generator ranges are rough planning bands for typical buildings.

Building Type Lighting Load (VA/ft²) Typical Standby Generator
Office 3.5 20–250 kW
Retail / Store 3.0 30–150 kW
Restaurant 2.0 40–120 kW
Warehouse 0.25–1.5 50–400 kW
Hospital 2.0 200–2,000 kW
Industrial / Loft 2.0 100–4,000 kW
Auditorium / Assembly 1.0 100–500 kW
Read it as a guide, not a spec sheet. The lighting load is the code minimum. The generator range is a band, because the real number depends on your HVAC, equipment, and whether you power the whole building or only critical loads. Run your actual building through the calculator for a firm figure.

The Code Number Is a Floor

Article 220 gives the prescriptive minimum for a compliant service. Real facilities often need more for harmonics, power factor, and growth — which is where an engineer and a load study come in. Use the calculator as your starting point, then confirm with a licensed professional.

Commercial Load Calculation

How to Calculate Electrical Load for a Commercial Building

To calculate electrical load for a commercial building, total the lighting at the NEC table value per square foot, add 180 VA per receptacle, add your HVAC at the larger of heating or cooling, and add motors at 125% of the largest unit. Apply the demand factors, then divide by your system voltage to get the service size in amps.

STEP 01

Occupancy & Lighting

Start with occupancy and square footage. Lighting is calculated at the minimum unit load from NEC Table 220.12 — the value applies even with LED fixtures installed.

STEP 02

Receptacles

Add 180 VA per outlet, then apply the demand factor: the first 10,000 VA at 100%, the remainder at 50%.

STEP 03

Show Windows & Signs

Show windows count at 200 VA per linear foot. Sign lighting at 1,200 VA minimum.

STEP 04

HVAC & Motors

Add HVAC from nameplate ratings — count only the larger of heating or cooling. Add motors at 125% of the largest motor; all others at 100%.

STEP 05

Continuous Loads & Service Size

Mark continuous loads (3+ hours) at 125%. Total the demand in VA, then divide by voltage (or voltage × 1.732 for three-phase) to get the service size in amps, rounded up.

Quick Summary

The Full Method in Code Order

1. Occupancy & square footage → lighting at Table 220.12
2. Receptacles: 180 VA each → first 10kVA at 100%, remainder at 50%
3. Show windows: 200 VA/ft • Signs: 1,200 VA min
4. HVAC: larger of heating or cooling • Motors: 125% of largest
5. Continuous loads at 125% • Total VA ÷ voltage = service amps

From Load to Generator

From Building Load to Generator Size

Your building's demand load in kVA is the starting point for backup power. Generators are rated in kVA at a 0.8 power factor, so the translation is direct: a building with 63 kVA of demand needs a generator whose kVA rating covers that demand with margin.

01

Size at 125% of Peak Demand

A generator that runs at 80% of its rating handles start-up surges and seasonal peaks without strain. A building with 63 kVA of demand lands in the 80–100 kVA class.

02

Mind the Motor Inrush

The largest motor — usually the AC compressor or a pump — draws 2–8× its running load at start. A soft starter or VFD needs far less headroom than a direct-on-line starter.

03

Pick Your Duty: Standby vs Prime

Standby sets run only during outages and can be sized closer to the load. Prime sets run continuously and carry extra margin for load swings. The calculator returns both.

04

Real Models — 8–4,000 kVA

Every class maps to a real model. A typical store lands on a 100 kVA silent diesel set in a soundproofed enclosure, with transfer switch and base tank, factory-direct.

05

Cost Range: $15k–$40k

A 100 kVA silent standby set with transfer switch and base tank runs roughly $15,000–$40,000 delivered, depending on site work and enclosure. A factory-direct quote lands your exact number.

06

Pre-Filled Quote

Use the calculator results as your starting point. Our engineers confirm the load and deliver a factory-direct quote with your numbers pre-filled — no markup, no surprises.

Common Errors

5 Commercial Sizing Mistakes

Our engineers see these five errors on commercial jobs more than any others. Avoid them and your service and generator will be sized right the first time.

01

Using Watts Where the Code Says VA

Mixing watts into a volt-ampere calculation undersizes conductors and breakers for inductive loads. Always use VA for code calculations.

02

Forgetting the Demand Factor

Adding every connected watt with no diversity oversizes everything. Demand load, not connected load, is the number that matters for service and generator sizing.

03

Counting Both Heating and Cooling

Heating and cooling don't run together — counting both inflates the service and the generator by a full class. Count only the larger of the two.

04

Skipping the Growth Margin

Buildings add equipment. A 15–25% reserve protects against a service that's obsolete the day you add an EV charger or a second AC zone.

05

Ignoring Motor Inrush & Derating

The AC compressor's start-up draw, plus altitude and temperature on a high site, both change the generator size. A VFD or soft starter shrinks it; a direct-on-line motor grows it.

Not sure your building's number is right? Our engineers will review your load and site and confirm the service and generator size before you spend anything. Talk to our engineers.

Let's talk

Get a Commercial Power Assessment

Our engineers will review your building’s load calculation, confirm the service size, and deliver a factory-direct price — no obligation, no hidden fees. Every quote includes the generator, automatic transfer switch, and soundproofed enclosure for a complete commercial standby solution.

Frequently Ask Questions

Get in touch with us
Leave a message
Contact Form Demo