Three-Phase kVA Formula
kVA = (√3 × Volts × Amps) ÷ 1,000
Line-to-line voltage × line current × 1.732, divided by 1,000.
Convert kW, kVA, amps, volts, and power factor instantly for single- and three-phase systems at 50 Hz or 60 Hz. Built on the same formulas electrical engineers use, every result maps to a real generator from 8–4,000 kVA. Built by Shandong Huali, a diesel generator manufacturer since 1999. Get a factory-direct quote with your calculated size pre-filled.
Factory-direct power since 1999.
A kVA calculator performs one essential job: it converts between the units used to describe electrical power. Three units matter in every sizing decision.
The real, usable power your equipment consumes. Motors, heaters, and lighting all use it.
The total power capacity the generator, transformer, or UPS must supply. This is the rating stamped on the equipment.
The current flowing at your system voltage, which determines cable size and breaker rating.
The relationship between kW, kVA, and amps depends on two things: the power factor of your load and whether the system is single-phase or three-phase. A good calculator handles all of it in one step.
kW to kVA, kVA to amps, amps to kVA, and volts — all on one page. No need for multiple tools.
Enter your load in kW or amps and it returns the kVA generator you need, mapped to a real Huali model.
Supports single-phase and three-phase at 50 Hz and 60 Hz — so the result is valid in your country, not just the US.
Every result ends in a free factory-direct quote, so you move from conversion to price in one step.
Convert kW, kVA, amps, volts, and power factor instantly. Works for single-phase and three-phase at 50 Hz or 60 Hz. Size your generator correctly, then request a quote.
Enter any two known values. The calculator fills in the rest using the standard power formulas.
Enter your total connected load. The calculator returns the required kVA, recommended generator class, and headroom margin.
This table gives the current for common kVA sizes at the three most common three-phase voltages. Use it to sanity-check a calculation, size a breaker, or select cable before you finalize. For any voltage or kVA outside this table, run it through the kVA to amps calculator above.
| kVA | Amps @ 230 V | Amps @ 400 V | Amps @ 480 V |
|---|---|---|---|
| 10 kVA | 25 A | 14 A | 12 A |
| 20 kVA | 50 A | 29 A | 24 A |
| 50 kVA | 126 A | 72 A | 60 A |
| 100 kVA | 251 A | 144 A | 120 A |
| 150 kVA | 377 A | 217 A | 180 A |
| 200 kVA | 502 A | 289 A | 241 A |
| 250 kVA | 628 A | 361 A | 301 A |
| 300 kVA | 753 A | 433 A | 361 A |
| 500 kVA | 1,255 A | 722 A | 601 A |
Manufacturers rate generators in kVA because the alternator's limit is about current, not watts. kVA = volts × amps captures that physical limit directly. The kW a generator delivers depends on your load's power factor, so the honest rating is the kVA value, with kW quoted at a reference power factor (usually 0.8). Compare generators on kVA first — it is the true capacity.
The 3-phase kVA formula is the foundation of every sizing decision. It uses line-to-line voltage and the square root of 3 (√3 ≈ 1.732):
kVA = (√3 × Volts × Amps) ÷ 1,000
Line-to-line voltage × line current × 1.732, divided by 1,000.
Unique to three-phase systems. Comes from the geometry of three phases spaced 120° apart. Omit it and you get only 58% of the true kVA — a 42% under-estimate that undersizes your generator.
A 400 V three-phase supply carrying 200 A per phase:
kVA = (1.732 × 400 × 200) ÷ 1,000 = 138.6 kVA
No √3 factor:
kVA = (Volts × Amps) ÷ 1,000
For comparison — single-phase current is roughly 73% higher per kVA at the same voltage.
Three-phase:
Amps = (kVA × 1,000) ÷ (√3 × Volts)
Single-phase:
Amps = (kVA × 1,000) ÷ Volts
The √3 factor is the most commonly skipped step in power calculations. Omitting it under-estimates power by about 42% — a direct path to an undersized generator. Use the converter above to run your own numbers in either direction.
Two forces push industrial generators to sizes that look "too big" on paper: power factor and motor starting.
A site full of motors and pumps runs at a lower power factor than one full of heating and lighting. At 0.8 PF you need 25% more kVA than your kW total; at 0.7 PF you need more than 40% more.
The extra kVA is not waste — it is the reactive power your motors and inductive loads genuinely require to magnetize their windings.
The locked-rotor current a motor draws in its first seconds is far above its running current. The peak, not the average, determines the generator size.
6–8× full-load current — the largest generator required. Use when no other starting method is available.
2–3× full-load current. A soft starter or star-delta reduces the starting surge roughly in half compared to DOL, often allowing a smaller generator.
A VFD draws 1–1.5× full-load current — the smallest generator required. Where a site can stagger-start its largest motors, the generator can be smaller still.
We see these five errors repeatedly in real-world projects. Avoid all of them and your generator sizing will be defensible from the start.
Omitting 1.732 in a three-phase calculation under-estimates power by about 42%. Always apply it for three-phase, and never for single-phase.
Three-phase kVA uses line-to-line voltage. Mixing the two gives a wrong result by a factor of √3.
Always divide by the power factor. A 100 kW load is not a 100 kVA generator — at 0.8 PF it is roughly 125 kVA.
A generator that carries your running load all day can still trip the instant a compressor's locked-rotor current hits it. Size for the largest start.
Running a generator at full load leaves no margin for surge, altitude, temperature, or growth. Always use the 20–25% headroom.
Not sure your calculation is right? Our engineers will review your load list and confirm the kVA before you spend anything. Talk to our engineers.
Our engineers will review your calculated kVA, confirm the specification, and deliver a factory-direct price — no obligation, no hidden fees. Every quote includes the generator, automatic transfer switch, and soundproofed enclosure for a complete commercial solution.
A: At 400 V line-to-line, a 100 kVA three-phase supply carries about 144 A per phase (100 × 1,000 ÷ (1.732 × 400)). At 480 V it is about 120 A; at 230 V it is about 251 A. The calculator returns the exact value for your voltage.
A: Divide the kW by the power factor: kVA = kW ÷ PF. At the standard 0.8 power factor, a 100 kW load needs 125 kVA. Our kW to kVA calculator above does this instantly.
A: kVA = (√3 × Volts × Amps) ÷ 1,000, using line-to-line voltage and line current. √3 is approximately 1.732. This is the formula used throughout this page and by every manufacturer’s sizing tool.
A: No. kVA is apparent power and kW is real power. They are linked by the power factor: kW = kVA × PF. A generator rated 100 kVA at 0.8 PF delivers 80 kW of usable power.
A: Because the alternator’s physical limit is current at a fixed voltage, which is exactly what kVA measures. The real kW a generator delivers depends on the power factor of your load, so the fixed rating is quoted in kVA.
A: A 125 kVA generator at 400 V three-phase provides about 180 A per phase (125 × 1,000 ÷ (1.732 × 400)). At 230 V three-phase it is about 314 A per phase.
A: At 0.8 power factor, 45 kW = 56 kVA. With a 25% safety margin you reach about 70 kVA, so a 75 kVA (60 kW) diesel genset is the right size. Our generator sizing calculator confirms this with your full load list.
A: Yes. Our range spans 8 kVA to 4,000 kVA in standard sizes, at 50 Hz or 60 Hz, single- or three-phase. If your calculated size falls between standard ratings, we offer OEM/ODM customization to match your exact specification.