Motor Current Calculator

3 Phase Motor Amps Calculator

A three-phase motor's nameplate gives you horsepower or kilowatts — but the cable, the breaker, and the generator are all sized in amps. That conversion, from mechanical power to running current, is the first calculation in every motor installation. Enter the motor's horsepower or kilowatts, the voltage, the efficiency, and the power factor — the tool returns the full-load amps (FLA) along with the kVA that current represents.

HP / kW input
FLA + kVA output
NEC 430.250 reference
Calculate Motor Amps
Free three-phase motor current calculator.
ShanHua Power

Motor Current Reference

Calculate full-load amps for three-phase motors — with NEC Table 430.250 values for code compliance.

25+ Years experience
8–4,000 kVA generator range
20+ Countries supplied
Motor Current

Full Load Amps (FLA) vs Starting Current: Which Sizes What

A motor has two very different currents, and confusing them is how installations go wrong. Full-load amps (FLA) is the running current — it sizes the cable, the breaker, and the continuous-load rating. Starting current is the locked‑rotor surge — it sizes the contactor, the starter, and the generator.

FLA Running Current

Full-load amps is the steady current the motor draws at rated output. It is modest, continuous, and it sizes the cable, the breaker, and the continuous-load rating.

Starting Current Locked‑Rotor Surge

The inrush surge — six to eight times the full-load amps for the first second or two of acceleration. It is violent, brief, and it sizes the contactor, the starter, and the generator.

Two Numbers Two Different Answers

FLA = running — "How many amps does my motor draw while running?"
Starting = starting — "How many amps does my motor draw while starting?"
You need both.

Get One Wrong and the Installation Fails

Get the FLA wrong and the cable runs hot — the breaker trips on overload or the insulation fails over time. Get the starting current wrong and the generator trips the moment the motor comes up to speed.

The full calculation for the starting side — locked‑rotor amps, starting methods, and starting kVA — lives on our companion motor starting current calculator, which takes the full‑load amps from here as its starting point.

Quick Reference

FLA vs Starting Current

01
FLA Sizes the Cable

Full-load amps determines the conductor size, the circuit breaker, and the overload protection settings. Use the 3 Phase Motor Amps Calculator to get it right.

02
Starting Current Sizes the Generator

Locked‑rotor amps determines the generator rating, the contactor, and the starter. This is the number that ensures the motor actually starts.

03
Confusing Them Is the Mistake

Designers who size the generator on FLA consistently under‑buy. The starting current is 6–8× the FLA — the generator must handle that surge, not just the running load.

04
Two Calculators, One Workflow

1. Use this page for FLA (cable & breaker).
2. Use the motor starting current calculator for the surge (generator).
Together they cover the complete installation.

3-Phase Motor Amps Calculator
Motor Current Calculator

How The 3-Phase Motor Amps Calculator Works

The formula takes the motor's mechanical output and walks it back to the electrical current the supply must deliver, accounting for the two losses along the way: efficiency and power factor.

From horsepower:
I = hp × 746 ÷ (√3 × V × n × PF)
From kilowatts:
I = kW × 1000 ÷ (√3 × V × n × PF)
Where I is the full‑load current in amps, V is the line‑to‑line voltage, η is the motor efficiency as a decimal, and PF is the power factor as a decimal. The √3 (1.732) is the three‑phase factor; for a single‑phase motor, drop it and use I = hp × 746 ÷ (V × η × PF).

Quick Reference

If you do not have the nameplate data, use 0.90 for efficiency and 0.85 for power factor — the typical values for a standard industrial motor.

Two rules of thumb:

  • 230 V three‑phase: about 2.5 amps per horsepower
  • 460 V three‑phase: about 1.25 amps per horsepower

The tool runs the exact figure for your numbers. The kVA the motor draws is then:

kVA = √3 × V × A ÷ 1000

and it is the kVA, not the amps alone, that the generator must carry.

Motor Horsepower Input

Enter the rated horsepower of your motor, along with the supply and motor parameters.

Typical: 0.90
Typical: 0.85

Motor Kilowatt Input

Enter the rated kilowatt output of your motor, along with the supply and motor parameters.

Typical: 0.90
Typical: 0.85
NEC Table 430.250 - Motor Full Load Current
NEC Reference

NEC Table 430.250: Motor Full Load Current by Horsepower

Here is the detail that separates a code-correct installation from a hopeful one: the code does not trust the nameplate.

For sizing conductors, switches, and branch-circuit protection, the NEC requires you to use the full-load current values in Table 430.250 (for three-phase motors), not the nameplate FLA. The table values are deliberately conservative, and they are almost always higher than the calculated figure — because they are built to cover the worst motor in each horsepower class, not your specific one.

Horsepower (hp) Amps at 230 V Amps at 460 V
1/2 hp2.2 A1.1 A
1 hp4.2 A2.1 A
3 hp9.6 A4.8 A
5 hp15.2 A7.6 A
7.5 hp22 A11 A
10 hp28 A14 A
15 hp42 A21 A
20 hp54 A27 A
30 hp80 A40 A
50 hp130 A65 A
75 hp192 A96 A
100 hp248 A124 A
150 hp360 A180 A
200 hp480 A240 A
Three things to notice:
  • The table runs higher than the formula. A 5 hp, 460 V motor calculates at about 6.1 A, but the NEC table says 7.6 A. You size the conductors to the table, not the nameplate.
  • Conductors use 125% of the table value. Per NEC 430.22, a continuous-duty motor's branch-circuit conductors are sized at 125% of the full-load current — so the 7.6 A becomes a 9.5 A conductor requirement.
  • The amps roughly double when the voltage halves. The same 50 hp motor draws 130 A at 230 V but only 65 A at 460 V — which is why lower-voltage installations mean larger cables, and why the generator's voltage matters too.
Motor Amp Chart & Worked Examples
Worked Examples

Motor Amp Chart & Worked Examples

Three examples, calculated with the formulas above, to show the shape of the answer.

Example 01

5 hp, 460 V, 90% η, 0.85 PF

Classic small pump motor
I = 5 × 746 ÷ (1.732 × 460 × 0.90 × 0.85) = 6.1 A

NEC table value: 7.6 A
125% for conductors: 9.5 A

✅ Current: 6.1 A
Example 02

11 kW, 415 V, 85% η, 0.90 PF

Common industrial motor
I = 11,000 ÷ (1.732 × 415 × 0.85 × 0.90) = 20.0 A

NEC table (approx. 15 hp @ 460 V is 21 A, similar)

✅ Current: 20.0 A
Example 03

7.5 kW, 400 V, 86% η, 0.90 PF

Smaller workshop motor
I = 7,500 ÷ (1.732 × 400 × 0.86 × 0.90) = 14.0 A

NEC table (approx. 10 hp @ 460 V is 14 A)

✅ Current: 14.0 A

For a quick reference across the range, the rule of thumb holds up: 1.25 amps per horsepower at 460 V — so a 100 hp motor is about 124 A, which is exactly what the NEC table says. Run the calculator for your exact voltage, efficiency, and power factor, and feed the resulting kVA into the generator path.

Let's talk

Get the Running Amps Right — and the Generator That Carries Them

Use the 3 phase motor amps calculator above, then check the starting surge with our motor starting current calculator, convert the kVA with our generator kVA to amps calculator, and find the machine with our generator sizing calculator.

Frequently Ask Questions

Get in touch with us
Leave a message
Contact Form Demo