3 Phase Power Calculator

3 Phase kW Calculator — Convert Amps to kW Instantly

Knowing the real power of a three-phase load is the first step in almost every generator sizing decision. This calculator converts voltage, current, and power factor into kilowatts (kW), and shows you the apparent power (kVA) and reactive power (kVAR) your generator set will actually need to supply.

kW, kVA & kVAR
Single / Three Phase
Power Factor Included
Calculate Now
Free tool for industrial and commercial load planning.
ShanHua Power

Factory-Direct Generator Solutions

Diesel generator sets for backup, commercial and industrial power.

25+ Years experience
8–4,000 kVA generator range
20+ Countries supplied
Three-Phase Basics

What Is Three-Phase Power?

Three-phase power is the standard method of generating, transmitting, and distributing alternating current (AC) electricity in industrial and commercial facilities. Instead of a single alternating waveform, a three-phase supply delivers three currents offset by 120 degrees.

kW Real Power

The portion of electricity that performs actual work — turning a motor shaft, heating an element, or lighting a space.

kVA Apparent Power

The total power the supply and generator must deliver. It is the vector sum of real power and reactive power.

kVAR Reactive Power

Power that inductive loads (motors, transformers) store and return each cycle without performing useful work.

Line-to-Line vs Line-to-Neutral Voltage

Line-to-line voltage is measured between any two of the three phase conductors and is the value used in three-phase power formulas. Line-to-neutral voltage is measured between one phase conductor and neutral and equals the line-to-line value divided by √3. For this calculator, enter the line-to-line voltage.

Key Concepts

The Power Triangle

1
kW — Real Power

The actual work performed. Measured by your utility meter. This is the number the calculator produces.

2
kVA — Apparent Power

Total power the generator must supply. Generator alternators are rated in kVA because their limit is current and voltage.

3
kVAR — Reactive Power

Power stored and returned by inductive loads. Raises kVA demand without raising kW output.

4
Power Factor (PF)

PF = kW ÷ kVA. A purely resistive heater has PF = 1.0. An inductive motor may sit at 0.7–0.9. The generator must supply more kVA than the kW rating suggests.

3 Phase kW Calculator

Convert Amps to kW Instantly

Enter your line-to-line voltage, current, and power factor to calculate real power (kW), apparent power (kVA), and reactive power (kVAR). Switch to single-phase mode or calculate amps from kW with a single click.

3 Phase kW Calculator

kWReal power
kVAApparent power
kVARReactive power
ACurrent

Results are estimates for planning. Confirm final sizing with an engineer.

Quick Reference

3 Phase kW to Amps Conversion Table

For a quick reference at the standard generator power factor of 0.8, the table below lists the full-load current for common generator kilowatt ratings at 400 V (IEC/global standard) and 480 V (North American industrial).

Generator kW Amps @ 400 V Amps @ 480 V
5 kW9.0 A7.5 A
10 kW18.0 A15.0 A
20 kW36.1 A30.1 A
50 kW90.2 A75.2 A
100 kW180.4 A150.4 A
200 kW360.8 A300.7 A
500 kW902.1 A751.8 A
Note: These values are estimates for balanced loads at 0.8 power factor. Motor starting currents, altitude, ambient temperature, and duty cycle all affect the final figure. Treat the table as a planning aid.
Worked Examples

Three-Phase kW Calculation Examples

Seeing the formula in action makes it easier to trust the result. Here are three common scenarios that show how the calculator arrives at its numbers.

EXAMPLE 1

415 V Motor at 0.9 PF

A three-phase motor draws 10 A at 415 V with a power factor of 0.9. kW = (1.732 × 415 × 10 × 0.9) ÷ 1000 = 6.47 kW.

EXAMPLE 2

480 V Industrial Load at 0.85 PF

A production line draws 30 A at 480 V with a power factor of 0.85. kW = (1.732 × 480 × 30 × 0.85) ÷ 1000 = 21.2 kW.

EXAMPLE 3

Full-Load Current of a 100 kW Generator

A 100 kW three-phase generator at 400 V and 0.8 power factor. Amps = (100 × 1000) ÷ (1.732 × 400 × 0.8) = 180.4 A.

Key Insight

From kW to Generator Selection

A kilowatt figure alone does not tell you which generator set to buy. Convert kW to kVA by dividing by the power factor: at 0.8 PF, a 100 kW load requires a 125 kVA generator. Add a 25% margin for starting surge and match to a standard rating.

Final generator selection should be checked against the complete load schedule, motor-starting sequence, power factor, site conditions, duty rating and selected engine-alternator combination before equipment is ordered.

Let's talk

Need a Generator for This Load?

At Shandong Huali Electromechanical Co., Ltd., we manufacture diesel generator sets engineered for continuous industrial operation, with over 25 years of experience and strict pre-delivery testing on every unit. If your calculation points to a load we can serve, our engineers will confirm the correct rating for your application.