Generator Sizing Calculator

Amps to kVA Calculator — Size Your Generator From Load Current

Every generator purchase starts with a load. If you already know how much current your equipment draws — from a nameplate, a clamp meter, or your panel schedule — this tool turns measured line current into kVA and kW for single-phase and three-phase systems.

Single & three-phase conversion
kW & kVA output
Generator sizing guidance
Calculate My Load in kVA
Free sizing tool for commercial and industrial projects.
ShanHua Power

Factory-Direct Generator Solutions

Diesel generator sets for backup, commercial and industrial power.

25+ Years experience
8–4,000 kVA generator range
20+ Countries supplied
Amps to kVA Basics

What Is Amps to kVA Conversion?

Amps to kVA conversion turns a measured current into apparent power. It answers the question every generator buyer faces: if my equipment draws 100 amps, how large a generator do I need? The conversion depends on current, voltage, and phase configuration — it does not require power factor.

3-Phase kVA = (√3 × V × A) ÷ 1000

Apparent power for a balanced three-phase system using line-to-line voltage. The √3 factor (1.732) accounts for the three-conductor delivery.

Single-Phase kVA = (V × A) ÷ 1000

Apparent power for a single-phase system. The √3 factor disappears because power is delivered across two conductors only.

Power Factor kW = kVA × PF

Power factor converts apparent power to real power. At 0.8 PF, 69.3 kVA equals 55.4 kW. PF does not affect the amps-to-kVA conversion itself.

Why √3 (1.732)?

The square root of three appears because a three-phase supply delivers power continuously across three conductors that are 120 degrees out of phase. For the same current, a three-phase system delivers 1.732× more kVA than a single-phase system. That is why industrial equipment and generator sets are overwhelmingly three-phase — more power per ampere of conductor.

Key Facts

Amps → kVA: What You Need to Know

01
PF Does Not Affect Conversion

kVA is apparent power. The kVA that corresponds to a given current is fixed by voltage and phase — power factor only enters when you convert to kW.

02
Line-to-Line vs Line-to-Neutral

The three-phase formula uses line-to-line voltage. If working from line-to-neutral, use kVA = (3 × VLN × A) ÷ 1000.

03
Unbalanced Loads

If phases carry unequal currents, size from the highest phase. Estimate as kVA = (√3 × V × highest-phase-amps) ÷ 1000.

04
Reverse Formula

To convert kVA to amps: Amps = (kVA × 1000) ÷ (√3 × Volts). Use this when you already have a generator and need its full-load current.

Conversion Tool

Amps to kVA Calculator

Convert measured line current into apparent power (kVA) and real power (kW) for single-phase and three-phase systems. Use the result to size a generator, check an existing load, or compare across voltage systems.

Enter Your Load Data

kVA Apparent power
kW Real power
A Line current
A Single-phase current

Results are estimates for planning. Confirm final sizing with an engineer.

How to use: Enter your measured current and system voltage. The calculator shows the required kVA and kW for your load. Use the result to match against a generator rating — then add margin for motor starting and site conditions.
Conversion Reference

Amps to kVA Conversion Table (3 Phase)

For quick reference, the table below lists three-phase apparent power for common line currents at 400 V (IEC/global standard) and 480 V (North American industrial). These values assume balanced loads at standard voltages.

Line Current (Amps) kVA @ 400 V kVA @ 480 V
10 A6.9 kVA8.3 kVA
25 A17.3 kVA20.8 kVA
50 A34.6 kVA41.6 kVA
100 A69.3 kVA83.1 kVA
150 A103.9 kVA124.7 kVA
250 A173.2 kVA207.8 kVA
500 A346.4 kVA415.7 kVA
1000 A692.8 kVA831.4 kVA
2000 A1385.6 kVA1662.8 kVA
Important: Altitude, ambient temperature, and motor starting surge all affect the final generator selection. Treat the table as a planning aid rather than a substitute for engineering review.

Example 1: A 100 A load at 400 V, three-phase — 69.3 kVA.

Example 2: A 150 A load at 440 V, three-phase — 114.3 kVA.

Example 3: The same 100 A at 240 V single-phase — 24 kVA. For the same current, three-phase delivers 1.732× more apparent power.

Sizing Method

How to Use Load Current to Size a Generator

The kVA figure from the calculator above is the starting point for selecting the right generator. Follow these five steps to turn your measured current into a practical generator recommendation.

STEP 01

Determine Your Load Current

Get the amps number from a nameplate full-load amps (FLA), a clamp-meter reading of the running load, or the sum of branch-circuit currents on your panel schedule. For motor-driven equipment, account for starting surge separately.

STEP 02

Convert to kVA

Enter the current and your supply voltage into the calculator above. For a three-phase system, the result is the apparent power your generator must supply. For single-phase, the formula removes the √3 factor.

STEP 03

Convert to kW

Multiply by power factor to see real power. At 0.8 PF, a 69.3 kVA load equals 55.4 kW. Generator sets are commonly rated in kVA at 0.8 power factor, so both numbers matter when comparing machines.

STEP 04

Add Sizing Margin

Do not run a generator at 100% of rated load. Aim for 70–80% loading for continuous duty, and add headroom for motor starting surge. A common rule is to size 20–25% above your steady-state kVA.

STEP 05

Match to a Standard Rating

Round up to the next standard generator rating — 80 kVA, 100 kVA, and so on. Browse our diesel generator sets from 8 kVA to 4000 kVA and confirm the correct machine with an engineer.