Transformer Calculator

Transformer Calculator — Size kVA, Amps & Turns Ratio

Every electrical system needs the right transformer. Enter your supply voltage, load voltage, and load current to calculate the kVA rating, full-load current, and turns ratio for single‑phase or three‑phase applications.

kVA sizing
Full-load current
Step-up & step-down
Calculate My Transformer Size
Free sizing tool for commercial and industrial projects.
ShanHua Power

Factory-Direct Transformer & Generator Solutions

Diesel generator sets and complete power systems from 8 kVA to 4,000 kVA.

25+ Years experience
8–4,000 kVA generator range
20+ Countries supplied
Transformer Sizing Basics

What a Transformer Calculator Does

A transformer calculator determines the kVA rating and full-load current a transformer must have for a given supply voltage, load voltage, and load. It answers the question every specifier faces: if my load draws 100 amps at 400 V, what transformer connects it to the 11 kV supply?

3‑Phase Balanced Loads

kVA = (√3 × Volts × Amps) ÷ 1000
The √3 factor accounts for the three-phase power distribution.

Single‑Phase Simple Loads

kVA = (Volts × Amps) ÷ 1000
For control transformers, lighting, and small single‑phase equipment.

Full‑Load Current Primary & Secondary

Amps = (kVA × 1000) ÷ (√3 × Volts)
Calculate current on either winding from the kVA and voltage.

Turns Ratio & Voltage Transformation

The turns ratio is the relationship between the primary and secondary windings: Np ÷ Ns = Vp ÷ Vs. A step‑down transformer reduces voltage and increases current; a step‑up transformer does the reverse. Generator applications commonly use step‑up transformers to feed medium‑voltage grids from a 400 V generator output.

Built for Real Projects

More Than a Basic Sizing Tool

01
Global Electrical Systems

Supports single‑phase and three‑phase systems at any voltage.

02
Starting & Growth Factors

Apply a diversity factor for motor inrush and future expansion headroom.

03
Standard Rating Matching

Results are rounded up to the nearest standard transformer kVA size in your region.

04
Generator Step‑Up Ready

Includes a preset for 400 V → 11 kV generator step‑up applications.

Sizing Tool

Transformer Calculator — kVA, Amps & Turns Ratio

Enter your primary and secondary voltages, load current or kVA, and apply a starting or growth factor. The tool calculates the required kVA, standard rating, full‑load currents, turns ratio, and real power.

Transformer Calculator

kVA Required
kVA Standard size
A Primary current
A Secondary current
:1 Turns ratio
kW Real power

Results are estimates for planning. Confirm final sizing with an engineer.

Standard Ratings

Standard Transformer kVA Ratings & Full‑Load Currents

Transformers are manufactured in standard kVA sizes. Always round up to the next available rating. The table below lists common single‑phase and three‑phase ratings, plus full‑load secondary currents at 400 V and 480 V.

Rating Single‑Phase Three‑Phase
Small1, 1.5, 2, 3, 5 kVA3, 6, 9, 15, 30 kVA
Medium7.5, 10, 15, 25 kVA45, 75, 112.5, 150 kVA
Large37.5, 50, 75, 100 kVA225, 300, 500, 750 kVA
Extra167, 200, 250, 333 kVA1000, 1500, 2000 kVA
Substation2500, 3000, 4000 kVA
Full‑load current table (3‑phase): 25 kVA → 36.1 A @ 400 V · 50 kVA → 72.2 A @ 400 V · 100 kVA → 144.3 A @ 400 V · 250 kVA → 360.8 A @ 400 V · 500 kVA → 721.7 A @ 400 V · 1000 kVA → 1443.4 A @ 400 V. At 480 V, currents are approximately 17% lower.
Worked Examples

Transformer Sizing — Real‑World Scenarios

These four examples show how the formulas come together in practice. Use them to check your own calculation before finalising a transformer specification.

Example 1

Step‑down: 480 V → 240 V, 60 A load

A 60 A three‑phase load at 240 V requires kVA = (1.732 × 240 × 60) ÷ 1000 = 24.9 kVA. Round up to the next standard three‑phase size: 30 kVA. Primary current at 480 V is approximately 36 A.

Example 2

Generator step‑up: 400 V → 11 kV

A 500 kVA generator set feeds an 11 kV grid. The transformer is rated at least 500 kVA (typically 630 kVA with margin). The 400 V side carries about 722 A, while the 11 kV side carries only about 26 A.

Example 3

Single‑phase control transformer

A 120 V, 50 A single‑phase control load requires kVA = (120 × 50) ÷ 1000 = 6 kVA. A standard 7.5 kVA single‑phase transformer covers it with margin.

Example 4

Motor load with starting inrush

A 40 A three‑phase motor at 400 V has a steady‑state load of about 27.7 kVA. Applying a 1.5 starting factor gives 41.6 kVA, so a 45 kVA transformer is the safe choice rather than a 30 kVA unit.

Let's talk

Complete Power Systems — Generator & Transformer Coordination

At Shandong Huali Electromechanical Co., Ltd., we manufacture diesel generator sets from 8 kVA to 4,000 kVA and design complete power systems — including the transformer coordination a generator‑fed network requires. With over 25 years of manufacturing experience and strict pre‑delivery testing on every unit, we help you specify the transformer and the generator as one coordinated system.

Frequently Ask Questions

Get in touch with us
Leave a message
Contact Form Demo