DC Wire Size Calculator

DC Wire Size Calculator 12V, 24V & 48V — AWG & mm²

Size DC conductors for battery, solar, and marine circuits. Our free calculator handles 12V, 24V, and 48V systems, checks ampacity and DC voltage drop with the 2× round-trip factor, and returns AWG, mm², and fuse sizing. Built by Shandong Huali, a diesel generator and DC-equipment manufacturer since 1999, with models from 8–4,000 kVA. Get a factory-direct quote with your specs pre-filled.

12V, 24V & 48V DC
AWG & mm² with fuse sizing
Battery, solar & marine modes
Size My DC Circuit
Free tool – get your AWG, mm², fuse, and a diesel quote.
Shandong Huali

Diesel Generator & DC Systems

Factory-direct power since 1999.

25+ Years experience
8–4,000 kVA generator range
20+ Countries supplied
DC Wire Sizing

What the DC Wire Size Calculator Does

A DC wire size calculator answers one question: what conductor must carry this DC current safely, over this distance, at this voltage? The answer has two parts, and the DC version of each is simpler than the AC version.

Ampacity Current Capacity

The maximum current a conductor can carry continuously before its insulation overheats. Same AWG chart for DC and AC — thermal limit doesn't care about alternation.

Drop DC Voltage Drop

Voltage lost due to resistance. DC has no power factor or reactance — pure resistance × round-trip path. Simple, but unforgiving.

Size Conductor Size

The result — the AWG number or mm² cross-section you order. A 30 A circuit needs 10 AWG for a short run; at 12 V over 5 m it forces 16 mm² (≈5 AWG).

DC Sizing Is Voltage-Drop Sizing

A 30 A circuit needs 10 AWG copper by ampacity alone. Run that same 30 A at 12 V over 5 m and the DC drop forces 16 mm² (≈5 AWG), because 3% of 12 V is only 0.36 V. DC sizing is almost always voltage-drop sizing.

DC-Specific

More Than a Chart

01
12V, 24V & 48V Presets

12v, 24v, and 48v wire size calculator in one tool.

02
Current or Wattage Input

Enter an inverter's wattage directly to get full-load DC amps.

03
2× Round-Trip Formula

Shows the formula, reports drop in both volts and percent.

04
AWG, mm² & Fuse

Returns AWG and mm², plus fuse sizing — the steps most guides forget.

DC Wire Size Calculator: 12V, 24V & 48V
DC Wire Sizing

DC Wire Size Calculator: 12V, 24V & 48V (Battery, Solar & Marine)

Size DC conductors for battery, solar, and marine circuits. Enter your voltage, current, and run length. The calculator returns AWG, mm², voltage drop, and fuse sizing.

Enter Your DC Circuit Details

Select a voltage preset or enter a custom voltage. The calculator applies the 2× round-trip DC voltage drop formula.

DC Applications

DC Wire Size by Application

The most common DC sizing questions in the field. Use these charts as a quick reference for battery-to-inverter, solar, marine, and generator start circuits. For exact sizing, run the DC wire size calculator above with your specific voltage, current, and run length.

Inverter (12 V) Full-Load Current Cable (1–2 m run) Fuse
400 W 33 A 6 AWG 40 A
750 W 63 A 4 AWG 80 A
1,000 W 83 A 2 AWG 150 A
1,500 W 125 A 1/0 AWG 200 A
2,000 W 167 A 2/0 AWG 250 A
3,000 W 250 A 4/0 AWG 400 A
At 24 V the current halves — a 2,000 W inverter draws about 83 A and runs on 2 AWG instead of 2/0. At 48 V the current quarters — same 2,000 W draws about 42 A and runs on 6 AWG. If the run stretches beyond 2 metres, step up one size for each extra 1–2 metres at higher currents.

Avoid Copper-Clad Aluminum (CCA)

CCA carries about 40% more resistance than pure copper, so it needs roughly two AWG sizes up to match copper's drop. Its connections can oxidize and heat under load. For battery, inverter, and solar runs, use pure copper — tinned marine-grade copper in wet or salt environments.

DC Modes

How to Use the DC Wire Size Calculator

The tool works in four DC modes, so it serves a solar installer, a marine electrician, an off-grid van builder, and a generator buyer without any of them fighting the interface.

12V / 24V / 48V

Voltage Presets

At 3% drop: 12V loses 0.36V, 24V loses 0.72V, 48V loses 1.44V. Higher voltage = lower current = smaller cable. Use 12V for automotive/RV/marine, 24V for telecom/trucks, 48V for solar & EV.

BATTERY

Battery & Inverter Mode

Enter inverter wattage — returns full-load DC current, cable, and fuse. Size on low-voltage cutoff (e.g. 10.5V for 12V), not nominal voltage. Fuse within 18 inches of the battery. Negative leg same as positive.

SOLAR

Solar (PV) Mode

NEC 690: size conductors at 125% of Isc. A 10A panel → 12.5A design current. DC drop budget: 2% (tighter than the general 3%). The size is almost always voltage-drop limited.

MARINE

Marine & Automotive

ABYC E-11: 3% on critical circuits (bilge, nav, electronics), 10% on non-critical. Marine cable = tinned stranded copper, 105°C insulation. Automotive = SAE tables, thinner insulation, not for engine compartments.

CUSTOM

Custom Voltage

Enter 36V, 72V, or any pack voltage. The calculator applies the same formula — only the drop budget changes. Higher voltage always means smaller cable for the same power.

Rule

Fuse Within 18 Inches of the Battery

A Class T or ANL fuse protects the short run where a short circuit is most likely. Size it at or below the cable ampacity for continuous duty, or to the inverter surge current where the cable is upsized. The negative leg must be the same size as the positive — it carries the same current and the same round-trip drop.

DC Formula

How to Calculate DC Wire Size

The DC voltage drop formula is Vd = 2 × L × I × R ÷ 1,000, where L is the one-way length in metres, I is the current in amps, R is the conductor resistance in Ω/km, and 2 accounts for the round trip. The drop as a percent is Vd ÷ V × 100, and it drives every DC sizing decision.

01

12V Boat Circuit — Voltage Drop Wins

A 30A fridge on 12V, run 5m. 3% budget = 0.36V. 16 mm² drops 2.9% — OK. 10 mm² drops 4.6% — over. Answer: 16 mm² (≈5 AWG). Ampacity alone would allow 10 AWG, but voltage drop wins.

02

24V Inverter — Ampacity Wins

A 2,400W inverter on 24V draws 100A over 2m. 100A needs 2 AWG (115A at 75°C). Drop is 0.9%. Ampacity wins. If continuous, apply 125% → step to 1 AWG.

03

48V Solar — 2% Budget

A 10A Isc panel → 12.5A design current (125% of Isc). Run 15m, 2% budget = 0.96V. 10 mm² drops 1.4% — OK. 6 mm² drops 2.4% — over. Answer: 10 mm² (≈7 AWG).

Limits

3% Branch · 2% Solar · 5% Total

Recommended limits: 3% on a branch circuit, 5% total from source to load, and 2% for solar DC runs. This page doubles as a DC voltage drop calculator: the same formula returns the size, the volts dropped, and the percent remaining in one pass. Ampacity first, voltage drop second — and the bigger conductor wins.

DC vs AC

DC vs AC Wire Size: What Changes

If you have sized AC wire before, the DC difference is smaller than you might think, and it lives entirely in the voltage-drop step. Ampacity is identical; the budget is what bites.

01

Ampacity Is Identical

The same Table 310.16 chart sizes a 12V DC circuit and a 240V AC circuit. The conductor's thermal limit doesn't know the difference.

02

DC Uses 2× Round-Trip

DC uses the same 2× round-trip rule as single-phase AC. What DC does not add is power factor and reactance — pure resistance only.

03

The Budget Is What Bites

A 240V AC circuit spends its 3% budget over 7.2V; a 12V DC circuit spends the same 3% over 0.36V. The same amps and metres that need 10 AWG at 240V need 4 AWG or larger at 12V.

04

AC Three-Phase Uses √3

Three-phase AC replaces the 2× round-trip with √3 (1.732). It drops about 13% less than single-phase on the same conductor, current, and distance.

For single- and three-phase AC sizing with power factor and the √3 rules, use the AC wire size calculator. This page is the DC side of that pair. Both feed the general wire size calculator, which returns DC and AC answers in both AWG and mm² in one pass.

Let's talk

Get a DC Cable & Battery Package Quote

Our engineers will review your DC circuit sizing, confirm the voltage drop, and deliver a factory-direct price — no obligation, no hidden fees. Every quote includes the cable, fuse, and battery package for your 12V, 24V, or 48V system, plus the generator behind the start battery.

Frequently Ask Questions

Get in touch with us
Leave a message
Contact Form Demo