Wire Sizing Reference

Wire Size Chart: AWG, Amps & Distance

Select the correct conductor for your load, voltage, and run length based on NEC Table 310.16 and IEC standards. Includes ampacity, voltage drop, and AWG-to-mm² conversion.

AWG & mm²
Ampacity & Voltage Drop
Copper & Aluminum
Calculate My Wire Size
Download the full chart as Excel, CSV, or PDF.
Shandong Huali

Generator & Cable Solutions

Diesel generator sets from 8 to 4,000 kVA with complete cable connection packages.

25+ Years experience
8–4,000 kVA generator range
20+ Countries supplied
Interactive Tool

Wire Size Calculator – AWG & mm²

Enter your load current, voltage, phase, and distance. The calculator selects the smallest conductor that meets both ampacity and voltage drop (≤3%) per NEC 310.16 and IEEE 141.

Enter Your Circuit Parameters

All inputs are required for an accurate recommendation.

Recommended Conductor

Calculation Results

Minimum Wire Size Enter parameters and click Calculate
Ampacity Basis
Voltage Drop
Actual Current Capacity
Recommended Breaker
Installation Note Adjust inputs above to size your circuit.

Based on NEC 310.16 (75°C terminations) and voltage drop per IEEE 141. Always consult local codes and a qualified electrician.

Reference Data

Comprehensive Reference Tables

Complete wire sizing data including NEC 310.16 ampacity, breaker pairings, voltage drop distances, and AWG‑to‑mm² conversion. Use these tables for quick look‑up or as a backup to the calculator.

Table A – NEC 310.16 Ampacity

Ampacity is the maximum current a conductor can carry continuously without exceeding its insulation temperature rating. In North America the governing values come from NEC Table 310.16. Ampacity depends on the conductor's temperature rating – the higher the rating, the more current the same wire can carry. The table below shows the 75°C column, the default for most breaker and equipment terminations per NEC 110.14(C). If you are not sure, size to the 75°C column and you will be safe in the vast majority of installations.

AWG / kcmilAmpacity (75°C)AWG / kcmilAmpacity (75°C)
14 AWG20 A1/0 AWG150 A
12 AWG25 A2/0 AWG175 A
10 AWG35 A3/0 AWG200 A
8 AWG50 A4/0 AWG230 A
6 AWG65 A250 kcmil255 A
4 AWG85 A350 kcmil310 A
3 AWG100 A500 kcmil380 A
2 AWG115 A750 kcmil475 A
1 AWG130 A1000 kcmil545 A
Which column should you use? The 60°C column applies to NM‑B (Romex) and UF‑B, most residential indoor wiring. The 75°C column is the default for anything landing on circuit‑breaker terminals. The 90°C column is a starting point for derating calculations, but the final rating is usually limited by the 75°C terminal. When in doubt, use the 75°C column.
Table B – Common Circuit Breaker to Wire Size

For quick everyday decisions, most people don't work backwards from ampacity – they start from the circuit breaker. This chart pairs standard breaker sizes with the correct copper conductor. It is the fastest way to answer "what size wire for X amps?"

BreakerCopper WireTypical Application
15 A14 AWGLighting, receptacles
20 A12 AWGKitchen, bathroom, garage
30 A10 AWGDryer, water heater
40 A8 AWGRange, EV charger
50 A6 AWGHot tub, welder
60 A6 AWGSubpanel feeder
70 A4 AWGLarge heater
80 A3 AWGCommercial feeder
100 A2 AWG100A subpanel
125 A1 AWGService entrance
150 A1/0 AWGService entrance
175 A2/0 AWGFeeder
200 A3/0 AWG200A service
225 A4/0 AWGLarge feeder
250 A250 kcmilService entrance
300 A350 kcmilIndustrial feeder
400 A500 kcmilIndustrial main
NEC 240.4(D) small conductor rule: 14 AWG tops out at a 15 A breaker, 12 AWG at 20 A, and 10 AWG at 30 A, regardless of ampacity table values. The chart above already respects this rule.
Table C – Max Distance for 3% Voltage Drop (240V, Copper)

Ampacity tells you the wire won't overheat. Voltage drop tells you the equipment at the end of a long run will still work. The NEC recommends no more than 3% voltage drop on a branch circuit and 5% total (feeder + branch). For a given gauge, the acceptable distance shrinks at lower voltages. At 120V, halve these distances – a run that holds 3% at 76 feet on 240V needs 14 AWG only up to roughly 38 feet at 120V.

BreakerWire SizeMax Distance (ft)Equivalent at 120V
15 A14 AWG7638
20 A12 AWG9145
30 A10 AWG9748
40 A8 AWG11557
50 A6 AWG14673
60 A4 AWG19497
100 A3 AWG14773
Rule of thumb: For runs over roughly 100 feet, go up one wire size for every additional 100 feet of distance at 120V, and about half that penalty at 240V. The safest approach is to size for the larger of the ampacity result and the voltage‑drop result.
Table D – AWG to mm² Conversion

If you work in a market that uses metric cable (IEC 60228 / BS 7671 wiring regulations), or you are buying imported equipment with metric conductors, you need this pairing. Most electrical wire size charts online are AWG‑only or mm²‑only; this table gives you both so you can read either system confidently.

AWG / kcmilmm² (approx)AWG / kcmilmm² (approx)
18 AWG0.82 AWG33.6
16 AWG1.31 AWG42.4
14 AWG2.11/0 AWG53.5
12 AWG3.32/0 AWG67.4
10 AWG5.33/0 AWG85.0
8 AWG8.44/0 AWG107.2
6 AWG13.3250 kcmil127
4 AWG21.2350 kcmil177
3 AWG26.7500 kcmil253
Important: When replacing an imported cable, match the nearest mm² size that meets both the ampacity and voltage‑drop requirements – do not simply convert the number, because standards round differently. Always verify with the manufacturer's data sheet.
Special Applications

DC, Generator & Material‑Specific Tables

Quick reference for low‑voltage DC systems, generator output cables, and copper‑vs‑aluminium sizing. Use these tables when the general charts don't cover your specific equipment.

12V / 24V / 48V DC Inverter Cable

Inverter Power12V (0–3 ft)12V (3–6 ft)24V (0–6 ft)48V (0–10 ft)
600 W8 AWG6 AWG10 AWG12 AWG
1000 W4 AWG2 AWG8 AWG10 AWG
1500 W1/0 AWG2/0 AWG6 AWG8 AWG
2000 W2/0 AWG3/0 AWG4 AWG6 AWG
3000 W4/0 AWG4/0 AWG1/0 AWG4 AWG
DC sizing note: Voltage drop is the dominant factor. For longer runs, go up one to two sizes. Always fuse within 18 inches of the battery.

Generator kVA → Cable Size (mm²)

Generator (kVA)Full‑Load Amps (415V, 3‑phase)Cu Cable (mm²)Al Cable (mm²)
15 kVA21 A46
25 kVA35 A610
40 kVA56 A1016
62.5 kVA87 A1625
100 kVA139 A3550
160 kVA223 A7095
200 kVA279 A95120
250 kVA348 A120185
320 kVA445 A150240
400 kVA556 A240300
Based on 75°C, 3% drop at standard lengths. For runs over 50 m, add one size. Always verify with the generator data sheet and local code.

Copper vs Aluminium – Size Comparison

Load (Amps)Copper (AWG)Aluminium (AWG)Al Cu‑equivalent
20 A1210+1 size
30 A108+1 size
50 A64+1 size
70 A42+1 size
100 A21/0+2 sizes
125 A12/0+2 sizes
150 A1/03/0+2 sizes
200 A3/0250 kcmil+2 sizes
225 A4/0300 kcmil+2 sizes
250 A250 kcmil350 kcmil+1 size
Aluminium requires anti‑oxidant compound and AL‑rated lugs. For long runs, aluminium can be cost‑effective, but copper is the safer default for critical circuits.
Let's talk

Download the Complete Wire Size Chart

Get the full reference in Excel, CSV, or PDF – offline, printable, and ready for the job site. No purchase required.

Frequently Ask Questions

Get in touch with us
Leave a message
Contact Form Demo