Transformer Amperage Reference

3 Phase Transformer Amperage Chart for Every kVA Size

Full-load current for every standard transformer from 3 to 2000 kVA at 208, 240, 400, 415, 480, and 600 V. Use the interactive chart or download the complete table as Excel, CSV, or PDF.

kVA to amps
Primary & secondary current
NEC 450 breaker sizing
Get My Transformer Amps
Download the full chart as Excel, CSV, or PDF.
Shandong Huali

Transformer & Generator Systems

Diesel generators from 8 to 4,000 kVA with transformer and distribution packages to match.

25+ Years experience
8–4,000 kVA generator range
20+ Countries supplied
Interactive Tool

3 Phase Transformer Full-Load Current

Enter the transformer kVA and secondary voltage. The calculator returns the full-load current per line conductor, the primary current, and the recommended NEC 450 breaker size.

Enter Transformer Parameters

All fields are required for an accurate calculation.

Full-Load Current

Calculation Results

Secondary Full-Load Current Per line conductor
Primary Current
Transformer kVA
Recommended Breaker (125%)
Min. Conductor (75°C)
Formula used: Amps = (kVA × 1000) ÷ (1.732 × V). Results are per line conductor in a balanced three-phase system.

Based on NEC 450.3(B) for transformer protection. Breaker size = 125% of full-load current, rounded up to standard size. Always verify with local code and a qualified engineer.

Reference Data

3 Phase Transformer Amperage Chart

Full-load current for every standard kVA size from 3 to 2000 kVA at common voltages. Includes formula, primary vs secondary current, single-phase comparison, and medium-voltage values.

How to Calculate Transformer Full-Load Amps

The full-load current is derived from the formula: Amps (3-phase) = (kVA × 1000) ÷ (1.732 × V). For single-phase, use Amps = (kVA × 1000) ÷ V. The 1.732 factor (√3) is the reason three-phase current differs from single-phase at the same kVA and voltage.

kVA208 V240 V400 V415 V480 V600 V
38.37.24.34.23.62.9
616.714.48.78.37.25.8
925.021.713.012.510.88.7
1541.636.121.720.918.014.4
2569.460.136.134.830.124.1
3083.372.243.341.736.128.9
45125.0108.364.962.654.143.3
50138.8120.372.269.660.148.1
75208.2180.4108.3104.390.272.2
100277.6240.6144.3139.1120.396.2
112.5312.3270.6162.4156.5135.3108.3
150416.0360.8216.5208.7180.4144.3
225624.3541.3324.8313.0270.6216.5
300832.5721.7433.0417.4360.8288.7
5001,3881,203722695.6601481
7502,0821,8041,0831,043902722
10002,7762,4061,4431,3911,203962
15004,1643,6082,1652,0871,8041,443
20005,5524,8112,8872,7822,4061,925
Standard kVA sizes: 3, 6, 9, 15, 25, 30, 45, 50, 75, 100, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000. Amps are per line conductor in a balanced three-phase system. Values are based on the formula I = kVA × 1000 ÷ (1.732 × V).
Primary vs Secondary Current

The same kVA flows through both primary and secondary, but current differs because voltage differs. Higher voltage → lower current; lower voltage → higher current. Always size each side separately at its own voltage.

Transformer kVAPrimary VoltagePrimary CurrentSecondary VoltageSecondary Current
45 kVA480 V54.1 A208 V125.0 A
75 kVA480 V90.2 A208 V208.2 A
100 kVA480 V120.3 A208 V277.6 A
112.5 kVA480 V135.3 A208 V312.3 A
150 kVA480 V180.4 A208 V416.0 A
300 kVA4160 V41.6 A480 V360.8 A
Key rule: Secondary current is always higher than primary current for a step-down transformer. The secondary feeder and breaker must be sized for the secondary current, not the primary current.
Single-Phase vs Three-Phase Transformer Amps

At the same kVA and voltage, three-phase current is lower by a factor of √3 (1.732). Mixing up the formulas leads to gross over- or under-sizing.

ConfigurationFormulaFull-Load Amps (75 kVA, 240 V)
Single-PhasekVA × 1000 ÷ V312.5 A
Three-PhasekVA × 1000 ÷ (1.732 × V)180.4 A
Why the difference? Three-phase power is distributed across three windings, delivering more power at the same current. Always confirm the phase count before using the formula.
Transformer kVA to Amps at Other Voltages

Medium-voltage primaries and other voltages are common in large plants and utility distribution. The formula works for any voltage; the table below gives examples at 2400 V and 4160 V.

kVA2400 V (A)4160 V (A)
30072.241.6
500120.369.4
1000240.6138.8
1500360.8208.2
2000481.1277.6
Pattern: Current falls as voltage rises. A 1000 kVA transformer draws 1,203 A at 480 V but only 138.8 A at 4160 V. For any other voltage, apply the formula I = kVA × 1000 ÷ (1.732 × V).
Application Guide

Transformer Sizing, Protection & Generator Pairing

Practical guidance for selecting the right transformer, sizing breakers per NEC 450, and pairing transformers with diesel generators for complete power systems.

How to Size a 3-Phase Transformer Method

Choosing the transformer starts with the load. Convert it to kVA, apply a safety factor, then round up to the next standard size. The full-load current table then tells you what the installed transformer draws.

  • Step 1 – Find the load in kVA: kVA = 1.732 × V × A ÷ 1000. If the load is in kW, divide by the power factor: kVA = kW ÷ PF. A 100 kW load at 0.8 PF needs 125 kVA of transformer capacity.
  • Step 2 – Apply a safety factor: For well-known loads use 1.0. For uncertain loads or future growth use 1.25. Multiply the calculated kVA by this factor.
  • Step 3 – Round up to the next standard size: A 71.9 kVA calculation becomes 75 kVA. A 120 kVA calculation becomes 150 kVA. Standard sizes: 3, 6, 9, 15, 25, 30, 45, 50, 75, 100, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000 kVA.
Load (kVA)Safety FactorRequired kVAStandard Transformer
71.91.071.975 kVA
71.91.2589.9100 kVA
120.01.0120.0150 kVA
120.01.25150.0150 kVA
250.01.0250.0300 kVA
250.01.15287.5300 kVA
Motor loads get special treatment: Motors draw 3–6 times their running current at startup. If a motor is more than 10% of the total load, double its kVA contribution in the sizing calculation, or oversize the transformer by 125–150%. Continuous loads should run at 80–90% of transformer rated capacity for long service life.

Transformer Fusing & Breaker Sizing NEC 450

Per NEC Article 450.3(B), transformers rated 1000 V or less are protected as follows: primary-only protection at 125% of primary FLA; secondary-only protection at 125% of secondary FLA; or primary at 250% and secondary at 125% when both are used.

TransformerPrimary FLA (480 V)125%Recommended Breaker
45 kVA54.1 A67.7 A70 A
75 kVA90.2 A112.8 A125 A
112.5 kVA135.3 A169.1 A175 A
150 kVA180.4 A225.5 A250 A
300 kVA360.8 A451.0 A500 A
Standard overcurrent device sizes: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500 A. Verify against the specific edition of your code and confirm with a qualified engineer.

Generator-to-Transformer Sizing Pairing

Pair a transformer with a kVA rating at least equal to the generator's kVA at the site power factor. The transformer carries the full generator output, so its full-load current is read directly off the generator's output current.

Generator kVAOutput (415 V)Transformer kVASecondary Cable (mm²)
8 kVA11.1 A9 kVA4
30 kVA41.7 A30 kVA10
100 kVA139.1 A100 kVA35
250 kVA347.8 A250 kVA120
500 kVA695.6 A500 kVA2×240
1000 kVA1,391 A1,000 kVA4×240
2000 kVA2,782 A2,000 kVA8×240
4000 kVA5,565 A4,000 kVA16×240
Cable sizes are planning values for XLPE copper conductors at roughly 125% of full-load current. The wire size chart carries the full ampacity and voltage-drop method. Generator and transformer are both rated in kVA, so the pairing is direct.
Let's talk

The Right Transformer Size Starts Here

The full-load current of a 3-phase transformer decides everything downstream: the breaker, the cable, the switchgear, and the generator. This chart gives you that number for every standard kVA at every common voltage.

Frequently Ask Questions

Get in touch with us
Leave a message
Contact Form Demo