Transformer Sizing Chart – kVA to Amps Full Load Current
Transformer Sizing Reference

Transformer Sizing Chart: kVA to Amps (Full Load Current)

This transformer sizing chart gives you full‑load current, standard kVA ratings, and the minimum transformer size for a motor load, all in one place. Pick the single‑phase or three‑phase table, find your kVA and voltage, and read off the full‑load amps. Then round up to the next standard size and, if the load includes a motor, confirm the transformer is large enough to start it.

kVA to amps conversion
Single & three‑phase
Motor starting capacity
View Full Chart
Free reference for engineers and specifiers.
Shandong Huali

Power Transformers & Generator Sets

We build power systems and publish free tools for engineers — transformer sizing, kVA to amps conversion, and motor starting calculations in one place.

8–4,000 kVA generator range
25+ Years experience
20+ Countries supplied
How to Read a Transformer Sizing Chart
Transformer Reference Guide

How to Read a Transformer Sizing Chart

A transformer sizing chart is a lookup table, not a calculation. Find the kVA in the left column, then read across to the column that matches your voltage. The number you land on is the full‑load current in amps on that side of the transformer.

kVA → Amps Look Up, Don't Calculate

Find the kVA in the left column, then read across to the column that matches your voltage. The number you land on is the full‑load current in amps on that side of the transformer.

Three‑Phase Rules of Thumb

At 480 V: roughly 1.2 amps per kVA.
At 208 V: roughly 2.8 amps per kVA.

Single‑Phase Rules of Thumb

At 480 V: roughly 2.1 amps per kVA.
At 240 V: roughly 4.2 amps per kVA.

Use the Table, Not the Rule of Thumb

The chart works because current follows a fixed relationship with kVA and voltage. A 75 kVA, 480 V three‑phase transformer draws 90.2 amps at full load; the same transformer at 208 V draws 208 amps. Lower voltage means higher current for the same kVA, which is why the secondary side of a step‑down transformer always carries the heavier conductor.

These are approximations. Use the tables below for any sizing decision rather than the rule of thumb.

Key Takeaways

How to Read the Chart

01
Find kVA, Read Voltage Column

Locate the transformer kVA in the left column, then read across to the voltage column that matches your system.

02
Lower Voltage = Higher Current

A 75 kVA transformer draws 90.2 A at 480 V but 208 A at 208 V. Lower voltage means more amps — and heavier conductors.

03
Three‑Phase Approximations

~1.2 A/kVA at 480 V • ~2.8 A/kVA at 208 V. Useful for quick checks — but always verify with the table.

04
Single‑Phase Approximations

~2.1 A/kVA at 480 V • ~4.2 A/kVA at 240 V. Use the table for final sizing decisions.

Transformer Full Load Current Chart – kVA to Amps
Transformer Reference Data

Transformer Full Load Current Chart (kVA to Amps)

The tables below list full‑load current in amps by kVA and voltage, for single‑phase and three‑phase transformers.

Single‑Phase Full Load Current
kVA 120 V 208 V 240 V 277 V 480 V 600 V
18.3 A4.8 A4.2 A3.6 A2.1 A1.7 A
325 A14.4 A12.5 A10.8 A6.3 A5.0 A
541.7 A24.0 A20.8 A18.1 A10.4 A8.3 A
7.562.5 A36.1 A31.3 A27.1 A15.6 A12.5 A
1083.3 A48.1 A41.7 A36.1 A20.8 A16.7 A
15125 A72.1 A62.5 A54.2 A31.3 A25.0 A
25208 A120 A104 A90.3 A52.1 A41.7 A
37.5313 A180 A156 A135 A78.1 A62.5 A
50417 A240 A208 A181 A104 A83.3 A
75625 A361 A313 A271 A156 A125 A
100833 A481 A417 A361 A208 A167 A
Three‑Phase Full Load Current
kVA 208 V 240 V 480 V 600 V
1541.6 A36.1 A18.0 A14.4 A
3083.3 A72.2 A36.1 A28.9 A
45125 A108 A54.1 A43.3 A
75208 A180 A90.2 A72.2 A
112.5312 A271 A135 A108 A
150416 A361 A180 A144 A
225625 A541 A271 A217 A
300833 A722 A361 A289 A
5001,388 A1,203 A601 A481 A
7502,082 A1,804 A902 A722 A
The pattern is consistent. Current halves each time the voltage doubles for the same kVA, so a 300 kVA transformer draws 361 amps at 480 V but 722 amps at 240 V. That difference drives conductor and breaker sizing on each side of the transformer.
Motor to Transformer Sizing Chart – HP to kVA
Transformer Sizing Reference

Motor to Transformer Sizing Chart (HP to kVA)

Motors are the trickiest load to size a transformer for, because a motor's starting current is several times its running current. The chart below lists the minimum transformer kVA for a three‑phase motor, along with the motor's full‑load current at 230 V and 460 V for reference.

Motor HP FLA @ 230 V FLA @ 460 V Min. Transformer kVA
1/22.0 A1.0 A0.9
3/42.8 A1.4 A1.2
13.6 A1.8 A1.5
1-1/25.2 A2.6 A2.1
26.8 A3.4 A2.7
39.6 A4.8 A3.8
515.2 A7.6 A6.3
7-1/222 A11 A9.2
1028 A14 A11.2
1542 A21 A16.6
2054 A27 A21.6
2568 A34 A26.6
3080 A40 A32.4
40104 A52 A43.2
50130 A65 A52
60154 A77 A64
75192 A96 A80
100248 A124 A103
125312 A156 A130
150360 A180 A150
200480 A240 A200
Two adjustments apply when the load is a motor. If the motor has a service factor above 1.0, increase the full‑load amps proportionally; a 1.15 service factor adds 15%. If the motor starts more than once per hour, add about 20% more kVA to cover the extra inrush. These factors are why the minimum kVA in the chart runs higher than the motor's running kVA alone would suggest.
Standard Transformer Sizes & Sizing Guide
Transformer Selection

Standard Transformer Sizes (kVA)

Transformers are only manufactured in standard ratings, so a calculated load almost never matches a catalog size exactly. You always round up to the next standard kVA.

01

Single‑Phase

Standard kVA sizes:

  • 1
  • 1.5
  • 2
  • 3
  • 5
  • 7.5
  • 10
  • 15
  • 25
  • 37.5
  • 50
  • 75
  • 100
  • 167
  • 200
  • 250
02

Three‑Phase

Standard kVA sizes:

  • 3
  • 6
  • 9
  • 15
  • 30
  • 45
  • 75
  • 112.5
  • 150
  • 225
  • 300
  • 500
  • 750
  • 1000
  • 1500
  • 2000
  • and larger

A calculated 63 kVA load rounds up to a 75 kVA transformer. A calculated 42 kVA single‑phase load rounds up to 50 kVA. Selecting the next standard size, not the exact calculated value, is the rule.

Sizing Guide

Transformer Sizing Rules and Worked Examples

Sizing a transformer follows a short sequence. List every connected load, sum their amperes or kVA, convert to kVA with the formula, then round up to the next standard size.

A

Formulas

Single‑phase: kVA = (V × I) ÷ 1000

Three‑phase: kVA = (V × I × √3) ÷ 1000

From kW: kVA = kW ÷ power factor

B

Three More Rules

Match the voltage: The primary voltage must equal the source, and the secondary must equal the equipment's required voltage.

Match the frequency: A transformer does not change 50 Hz to 60 Hz — supply and load must agree.

Derate for the environment: Dry‑type transformers lose roughly 1% of rating for each degree Celsius above 40°C ambient and about 3% per 1000 meters above 1000 m elevation.

Worked Example

Three‑Phase 208 V, 175 A → 75 kVA

A three‑phase 208 V load drawing 175 amps works out to:

kVA = 1.732 × 208 × 175 ÷ 1000 ≈ 63 kVA

That rounds up to the 75 kVA standard size.

A single‑phase 240 V load drawing 175 amps works out to 240 × 175 ÷ 1000 ≈ 42 kVA, which rounds up to 50 kVA.

Once you have the kVA, the chart above gives you the full‑load current for conductor and breaker sizing. For the complete workflow, including demand factor and NEC 450.3 overcurrent protection, use our transformer sizing calculator.

Power System Coordination

Transformer Sized, Now Size the Generator

A transformer and a generator are two halves of the same power system, and they are usually sized together. The transformer steps voltage up or down; the generator supplies the source. If the facility loses utility power, the generator must carry the same load the transformer serves, and it must start any motors in that load.

01

Same Load, Two Components

The transformer steps voltage up or down; the generator supplies the source. If the facility loses utility power, the generator must carry the same load the transformer serves.

02

Motors Force Both Larger

A motor that forces a larger transformer also forces a larger generator, because the generator must deliver the motor's starting surge without an excessive voltage dip. Size the transformer first with this chart, then size the generator to match the same load.

Let's talk

About Shandong Huali

Shandong Huali Electromechanical Co., Ltd. manufactures diesel generator sets, dust-suppression equipment, and industrial automation systems, with over 25 years of experience and exports to more than 20 countries. We publish free electrical reference tools to help engineers and buyers specify power systems correctly.

Frequently Ask Questions

Get in touch with us
Leave a message
Contact Form Demo