Transformer Impedance
ZT = uk · Un² / SrT = 0.06 × 400² / 1,000,000 = 9.6 mΩ
When a fault occurs in an electrical network, the short-circuit current can reach tens of thousands of amps in milliseconds — enough to destroy switchgear if not rated correctly. IEC 60909 is the international standard that tells you exactly how to calculate that current, used across Europe, Asia and most of the world.
Diesel generator sets from 8 kVA to 4,000 kVA with subtransient reactance specified for every machine.
IEC 60909 is the international standard titled Short-circuit currents in three-phase AC systems, published by the International Electrotechnical Commission. Part 0 (IEC 60909-0:2016) sets out the calculation method for both low-voltage (up to 1 kV) and high-voltage three-phase systems at 50 Hz or 60 Hz.
The standard's core idea is the equivalent voltage source method. Instead of modelling the entire network in detail, IEC 60909 lets you replace everything upstream of the fault with a single ideal voltage source behind a single equivalent impedance. The short-circuit current is then simply:
This matters because it makes short circuit calculation practical. You don't need a load-flow model or a transient simulation; you need the rated data of your equipment — the transformer's impedance, the generator's subtransient reactance, the cable's resistance and reactance — and the standard does the rest. Two results are always calculated: maximum short-circuit current (using cmax) for equipment rating, and minimum short-circuit current (using cmin) for relay coordination.
Every IEC 60909 short circuit calculation starts from the initial symmetrical short-circuit current formula. The voltage factor c deliberately overstates the source voltage so that the maximum current is always conservative for equipment rating.
The master value from which all other currents are derived:
For a simple radial network fed from a single source, the impedance is a straightforward sum: Zk = Zsource + ZT + Zcable + …
The signature of the IEC 60909 method. It deliberately overstates the source voltage so that the maximum short-circuit current is always conservative.
| Nominal Voltage Un | cmax (max. current) | cmin (min. current) |
|---|---|---|
| Low voltage (100 V – 1 kV) | 1.05 (6%) or 1.10 (10%) | 0.95 |
| Medium voltage (>1 kV – 35 kV) | 1.10 | 1.00 |
| High voltage (>35 kV) | 1.10 | 1.00 |
Use cmax for rating and withstand checks, and cmin for protection-sensitivity checks.
The initial symmetrical current I″k is only the start. IEC 60909 derives a family of currents from it, each used to size a different piece of equipment — from breaker interrupting rating to thermal withstand of cables and busbars.
| Symbol | Name | Formula / Basis | What It Sizes |
|---|---|---|---|
| I″k | Initial symmetrical | I″k = c·Un / (√3·Zk) | Master value; basis for all others |
| ip | Peak (make) current | ip = κ·√2·I″k | Mechanical bracing, busbar withstand, breaker close-and-latch |
| Ib | Symmetrical breaking current | Ib = μ·I″k | Breaker interrupting rating |
| Ik | Steady-state current | Ik = I″k × (steady-state factor) | Generator/relay coordination, long-time settings |
| Ith | Thermal equivalent current | Ith = I″k × √(m + n) | Thermal withstand of cables, busbars, transformers |
Let's work a complete example so the method is concrete. Calculate the maximum short-circuit current at the 400 V busbar of a 1000 kVA transformer (20 kV / 400 V, uk = 6%), using cmax = 1.05.
ZT = uk · Un² / SrT = 0.06 × 400² / 1,000,000 = 9.6 mΩ
KT = 0.95·cmax / (1 + 0.6·xT)
= 0.95×1.05 / (1+0.6×0.06) = 0.963
ZTK = 0.963 × 9.6 = 9.24 mΩ
I″k = cmax·Un / (√3·Zk) = 1.05×400 / (1.732×9.24×10⁻³) = 26.3 kA
Transformer-fed fault, R/X ≈ 0.1, so κ ≈ 1.7.
ip = κ·√2·I″k
= 1.7 × 1.414 × 26.3
≈ 63 kA
A breaker on this busbar must interrupt at least 26.3 kA and withstand a 63 kA peak. Motor contributions would be added if present.
For a generator-fed system, the fault level is set by the generator's subtransient reactance X″d, not by an infinite bus. A 1000 kVA generator with X″d = 15% delivers roughly 1 / 0.15 = 6.7× its rated current — about 9.7 kA at 400 V — far lower than the transformer example above. This is the critical factor when sizing switchgear on generator-fed or islanded systems.
North America uses ANSI/IEEE C37; most of the rest of the world uses IEC 60909. Both reduce the network to a voltage source behind an impedance, but they differ in enough details that the results — typically 5–15% apart — can change an equipment rating.
| Parameter | IEC 60909 | ANSI / IEEE C37 |
|---|---|---|
| Base current | Initial symmetrical RMS (I″k) | Symmetrical RMS at contact-parting time |
| Voltage source | Voltage factor c (cmax = 1.05–1.10) | ~1.0 pu (max operating voltage) |
| Peak current | ip = κ·√2·I″k (κ depends on X/R) | ip = 1.6 × Isym (fixed) |
| DC decay | Via time constant τ | Integrated via X/R ratio |
| Impedance corrections | Extensive (KT, KG, KM, KS) | Limited temperature corrections |
| Motor contribution | Included with μ and q decay factors | Separate, with reactance multipliers |
ShanHua Power has manufactured diesel generator sets since 1999, with a range spanning 8 kVA to 4,000 kVA and certifications to ISO9001, CE, and CCC. We specify the subtransient reactance and short-circuit contribution of every machine we build — and help you select switchgear rated to interrupt it.
A: IEC 60909 is the international standard for calculating short-circuit currents in three-phase AC systems at 50 Hz or 60 Hz, covering low-voltage and high-voltage networks. Part 0 (IEC 60909-0:2016) defines the equivalent voltage source method and the voltage factor c.
A: Use the equivalent voltage source method: I″k = c · Un / (√3 · Zk), where c is the voltage factor, Un is the nominal voltage, and Zk is the total short-circuit impedance to the fault. Apply the transformer (KT) and generator (KG) correction factors to the impedances first.
A: The voltage factor c artificially raises the source voltage to guarantee a conservative maximum current. For low voltage it is 1.05–1.10 (cmax) and 0.95 (cmin); for medium and high voltage it is 1.10 (cmax) and 1.00 (cmin).
A: I″k is the initial symmetrical short-circuit current, ip is the peak current, Ib is the symmetrical breaking current, and Ik is the steady-state current. They size switchgear withstand, breaker interrupting rating, and relay coordination respectively.
A: A generator’s contribution is limited by its subtransient reactance X″d, so it typically delivers only 6 to 12 times its rated current — much less than a utility “infinite bus” source. This is the key factor when sizing switchgear on a generator-fed system.
A: IEC 60909 applies a voltage factor c and calculates the initial symmetrical current with extensive correction factors, while ANSI/IEEE C37 uses a ~1.0 pu source and a fixed 1.6× peak multiplier. Results differ by roughly 5–15%, and the two must not be cross-substituted.