Search, filter, and export the complete grid standard reference for 200+ countries. Single and three-phase voltage, 50 Hz vs 60 Hz, and plug types — all in one searchable database. Download the full chart as Excel, CSV, or PDF.
Diesel gensets from 8 to 4,000 kVA, built for any voltage and frequency standard. ISO9001, CE, CCC certified.
A reference table that maps every country to its nominal mains electricity standard — the single-phase voltage, three-phase voltage, frequency (Hz), and plug type. It is the specification input for any generator sold or installed outside its manufacturing country.
A 230 V single-phase system and a 400 V three-phase system require different alternator windings and different generator models.
A 50 Hz set runs at 1,500 rpm on a four-pole alternator; a 60 Hz set runs at 1,800 rpm. The frequency determines the engine's governed speed.
Two countries can share 230 V, 50 Hz and use different sockets. The plug type varies independently of voltage and frequency.
The generic "mains voltage by country" tables online answer the consumer question. This database answers the generator question: it pairs every country standard with the build that produces it, so the lookup flows straight into a specification. Three values matter most to a generator buyer — voltage, frequency, and plug type — and this database delivers all three in one searchable reference.
Every nation with a published grid standard. Single-phase and three-phase voltages, frequency, and plug type included.
Filter to see all 50 Hz countries, all 60 Hz countries, or every market that accepts a 400 V three-phase build.
Enter a voltage and frequency — such as 400 V at 50 Hz — and the tool returns every country that matches, confirming one generator model serves an entire export region.
Export the full dataset as Excel, CSV, or PDF for your export documentation, engineering handoffs, and project records.
Filter by country name, by frequency (50 Hz or 60 Hz), or by voltage band. The tool returns matching grid standards for export specification. The full dataset covers 200+ countries.
| Country | 1-Phase V | 3-Phase V | Frequency | Plug |
|---|---|---|---|---|
| United States | 120 | 208 / 480 | 60 Hz | A / B |
| Canada | 120 | 208 / 480 | 60 Hz | A / B |
| Mexico | 127 | 220 | 60 Hz | A / B |
| United Kingdom | 230 | 400 | 50 Hz | G |
| France | 230 | 400 | 50 Hz | C / E |
| Germany | 230 | 400 | 50 Hz | C / F |
| China | 220 | 380 | 50 Hz | A / C / I |
| Japan | 100 | 200 | 50 / 60 Hz | A / B |
| Saudi Arabia | 230 | 400 | 60 Hz | G |
| United Arab Emirates | 230 | 400 | 50 Hz | G |
| Australia | 230 | 400 | 50 Hz | I |
| India | 230 | 400 | 50 Hz | C / D / M |
| Brazil | 127 / 220 | 380 | 60 Hz | C / N |
| Nigeria | 230 | 400 | 50 Hz | D / G |
| Philippines | 220 | 380 | 60 Hz | A / B / C |
| Russia | 220 | 380 | 50 Hz | C / F |
| Cuba | 110 / 220 | 190 / 220 | 60 Hz | A / B / C / L |
| South Korea | 220 | 380 | 60 Hz | C / F |
| Italy | 230 | 400 | 50 Hz | C / F / L |
| Spain | 230 | 400 | 50 Hz | C / F |
| South Africa | 230 | 400 | 50 Hz | C / D / M / N |
| Egypt | 220 | 380 | 50 Hz | C / F |
| Pakistan | 230 | 400 | 50 Hz | C / D / G |
| Malaysia | 230 | 400 | 50 Hz | G |
Frequency splits the world into two camps, and the boundary follows history more than geography. The decision of whether your generator must run at 1,500 rpm (50 Hz) or 1,800 rpm (60 Hz) determines the engine speed, the governor, and the alternator configuration.
50 Hz countries include most of Europe, Asia, Africa, Australia, and New Zealand, plus Russia and the CIS. The 230 V, 50 Hz standard dominates this camp, with 220 V and 240 V as older or regional variants. If you export to Africa, the Middle East, Southeast Asia, or the European market, the default build is 50 Hz.
60 Hz countries include North America, Central America, parts of South America, the Caribbean, Japan west of the 60 Hz line, South Korea, the Philippines, and Saudi Arabia. The dominant standards are 120 V, 60 Hz and 127 V, 60 Hz single-phase, with 208 V, 480 V, and 220 V three-phase outputs.
The frequency is not arbitrary. It is set by engine speed on a four-pole alternator:
So "50 Hz vs 60 Hz countries" is really a question of whether your generator must run at 1,500 or 1,800 rpm, and whether your alternator and governor are built for it.
Dual‑standard countries complicate the map. Japan runs 100 V on both frequencies: 50 Hz in the east (Tokyo region) and 60 Hz in the west (Osaka region). Brazil uses 127 V or 220 V at 60 Hz depending on the state. Cuba lists 110 V and 220 V, both at 60 Hz.
Voltage has its own families, and they do not line up neatly with frequency. Understanding the 110–127 V and 220–240 V families — and their exceptions — is essential for specifying the correct generator alternator.
The 110 to 127 V family covers North America, parts of Latin America, and the Caribbean: 110 V, 115 V, 117 V, and 127 V nominal. Jamaica and Barbados use 115 V at 50 Hz — a deliberate exception in a 60 Hz region. Mexico uses 127 V at 60 Hz.
The 220 to 240 V family covers most of the rest of the world. China, Russia, and much of the CIS list 220 V at 50 Hz. Most of Europe, Asia, Africa, and Oceania list 230 V at 50 Hz, and the United Kingdom and Australia use 230 V as the nominal standard.
Three 60 Hz voltage exceptions sit inside the 50 Hz world: Montserrat, Saint Kitts and Nevis, and Antigua and Barbuda run 230 V at 60 Hz. A generator built for 230 V, 50 Hz will not directly power them, and a 120 V, 60 Hz build will not either.
For large installations, three‑phase output scales past the low‑voltage range. Medium‑voltage standards include 3.3 kV (Japan and Korea), 6.6 kV and 11 kV (much of Asia and the Middle East), and 4.16 kV and 13.8 kV (North America).
The country table tells you the destination standard. Configuring the generator to produce it is a four‑step process — exactly what the engineering team does on every export order.
50 Hz = 1,500 rpm • 60 Hz = 1,800 rpm. This selects the engine's rated speed, governor, and flywheel — before voltage.
12‑lead alternator reconfigures to 400 V / 230 V, 415 V / 240 V, or 480 V / 277 V for the destination standard.
400 V ÷ 50 Hz = 8.0 • 480 V ÷ 60 Hz = 8.0. The AVR holds this ratio under load at the destination.
100% load test at the exact voltage and frequency of the destination before shipping. Test record ships with the set.
Switchable set runs 1,500 or 1,800 rpm via electronic governor. One unit serves both 50 Hz and 60 Hz markets.
A mismatched frequency is not a minor nuisance. It damages equipment in three predictable ways, and the fix is not an adapter — it's either a frequency converter or a correctly built generator.
A 60 Hz motor fed with 50 Hz power runs roughly 17% below rated speed. Cooling fans slow, heat builds. A 50 Hz motor on 60 Hz runs 20% fast, accelerating wear.
A transformer sized for one frequency experiences higher core flux density on the other, raising losses and core temperature. A silent failure mode that shortens life.
Fans, pumps, and blowers are cube‑of‑speed loads. A small speed change produces a large power change — a load can draw far more than the generator is rated for.
Get the full generator voltage and frequency by country database in Excel, CSV, or PDF — 200+ countries with single and three-phase voltages, 50 Hz / 60 Hz, and plug types. Also receive a free factory-direct quote for a generator configured to your destination grid.
A: The United States uses 120 V single-phase and 208 V or 480 V three-phase, at 60 Hz. This is the anchor of the 60 Hz world, and North American generators are built to it.
A: The United Kingdom uses 230 V single-phase and 400 V three-phase, at 50 Hz, with a type G socket. Note the 415 V / 240 V variant for some industrial three-phase installations.
A: No, not directly. The frequencies are incompatible, and the equipment on the load side is built for one or the other. A frequency converter or a correctly built generator is required. Confirm the country standard in the database before ordering.
A: Not without derating. The motor slows by roughly 17%, cooling suffers, and full-load torque demand can overload it. For constant-speed or centrifugal loads, treat a frequency change as a redesign, not a setting.
A: A diesel generator produces the frequency set by its engine speed and alternator pole count. On a four-pole alternator, 1,500 rpm produces 50 Hz and 1,800 rpm produces 60 Hz. The generator frequency by country determines which speed you order.
A: The split traces to early electrical history. North America standardized around 110 V for incandescent lighting and kept it as the nominal 120 V standard. Europe and much of the rest of the world standardized higher voltages, which transmit more power for the same copper, and settled on 220 V to 240 V. The two families persist today in the standards table.
A: Match the destination in four steps: set the frequency via governor speed (1,500 rpm for 50 Hz, 1,800 rpm for 60 Hz), reconnect the alternator for the destination voltage, hold the correct V/Hz ratio with the AVR, and factory-test at the destination standard. Huali does all four on every export order.
A: A dual-frequency generator runs at either 1,500 or 1,800 rpm through an electronic governor and programmable ECU, holding the V/Hz ratio at both speeds. It serves mixed 50 Hz and 60 Hz markets from one unit, which suits distributors and contractors with work across regions.