Generator Cable Size Calculator

Find the Right Cable mm² & AWG for Your Generator

Enter your generator rating, voltage, phase, and cable length to get the minimum safe conductor size in mm² and AWG, plus recommended breaker rating and voltage drop.

Copper & aluminum
1‑phase & 3‑phase
Voltage drop included
Calculate Cable Size
Free sizing tool for commercial and industrial projects.
ShanHua Power

Factory-Direct Generator Solutions

Diesel generator sets and full connection support from 8 kVA to 4,000 kVA.

25+ Years experience
8–4,000 kVA generator range
20+ Countries supplied
Cable Sizing Basics

What a Generator Cable Size Calculator Does

A generator cable size calculator converts your generator rating, voltage, phase, and cable length into a practical conductor recommendation using ampacity, voltage drop, and a safety margin.

Ampacity Current‑carrying capacity

The maximum continuous current a conductor can carry without exceeding its temperature rating.

Voltage Drop Conductor loss

The reduction in voltage along the cable length. For long runs, voltage drop often determines the minimum cable size.

Safety Margin NEC 125% rule

Continuous loads require a 125% safety factor so the conductor is not operating at its absolute limit.

From Generator Rating to Recommended Cable Size

The calculator combines the full‑load current, a 125% safety margin, the conductor's ampacity, and the voltage drop over the cable length. The result is a recommended cable size in mm² and AWG, plus a matching breaker rating.

Built for Real Projects

More Than a Basic Wire Size Tool

01
Copper & Aluminum

Select the conductor material and see the size difference side by side.

02
1‑Phase & 3‑Phase

Supports single‑phase and three‑phase systems at 50 Hz and 60 Hz.

03
Voltage Drop & Breaker

Includes actual voltage drop percentage and a recommended breaker rating for the selected cable.

04
From Size to Quote

Use the result as the basis for a factory‑direct generator and cable package quotation.

Cable Sizing Tool

Generator Cable Size Calculator

Enter your generator rating, system voltage, phase, cable length, and conductor material. The calculator returns the minimum safe cable size in mm² and AWG, plus voltage drop and breaker rating.

Enter Your System Parameters

All fields are required. The result updates when you click "Calculate Cable Size".

Enter kVA (or kW with power factor below)
Typical generator PF = 0.8
230, 400, 415, 480, or custom
Metres from generator to load
Reference Table

Generator kVA to Cable Size Chart

Quick reference for three‑phase, 415 V generators at 0.8 PF using XLPE‑insulated copper cable. Use this as a starting point, then confirm with the calculator for your exact voltage, length, and material.

Generator Rating Full‑Load Current Recommended Copper Cable
15 kVA20 A4 mm²
25 kVA35 A6 mm²
40 kVA55 A10 mm²
62.5 kVA87 A16 mm²
82.5 kVA115 A25 mm²
100 kVA140 A35 mm²
125 kVA175 A50 mm²
160 kVA225 A70 mm²
200 kVA280 A95 mm²
250 kVA350 A120 mm²
Important: Ampacity values assume free‑air installation at 25 °C. Higher temperatures, conduit, buried cable, or grouped circuits all reduce safe current and may require a larger conductor.
Manual Sizing Method

How to Calculate Generator Cable Size

Follow this four‑step method to move from your generator rating to a practical cable size. The calculator automates the process, but understanding the method helps you verify the result.

STEP 01

Find the Full‑Load Current

For three‑phase: A = (kVA × 1000) ÷ (1.732 × V). For single‑phase: A = (kVA × 1000) ÷ V. If your generator is rated in kW, convert: kVA = kW ÷ PF.

STEP 02

Apply a Safety Margin

Continuous loads require a margin. Per NEC, size at 125% of full‑load current. For a 250 kVA, 415 V three‑phase set, 347.7 A × 1.25 = 434.6 A.

STEP 03

Size by Ampacity

Choose the smallest standard conductor whose ampacity meets or exceeds the adjusted current. For 435 A, a copper 240 mm² cable (490 A) is suitable.

STEP 04

Check Voltage Drop

For long runs, voltage drop often dictates the size. Use A = (k × ρ × I × L) ÷ VDallowed where k = 2 (1‑phase) or 1.732 (3‑phase), ρ = resistivity, and VDallowed = V × allowed %.

FINAL

Choose the Larger Size

The final cable size is the larger of the ampacity result and the voltage‑drop result, rounded up to the next standard IEC size: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240 mm².

Worked Example

250 kVA, 415 V, Three‑Phase, Copper, 30 m

Full‑load current = 347.7 A. With 125% margin = 434.6 A. Ampacity points to 240 mm² copper. Voltage drop with 240 mm² at 30 m is only 0.35%, so ampacity governs. Final size = 240 mm² (4/0 AWG).

Sizing Factors

Factors That Affect Generator Cable Sizing

A cable's current‑carrying capacity is not fixed. These variables can force you to select a larger conductor than the base chart suggests.

01

Ambient Temperature

As surrounding air temperature rises, the cable dissipates less heat. A cable rated at 25 °C carries noticeably less current at 40 °C or 45 °C, common in hot climates and enclosed plant rooms.

02

Installation Method

Free‑air cable on tray or ladder carries the most current. The same conductor in conduit, in a duct, or directly buried carries less. Always match the installation method to the correct ampacity table.

03

Cable Grouping

When several circuits run together in one conduit or trench, cables heat each other. Bundled cables require derating, sometimes by 20% or more.

04

Load Type

Motor‑starting and non‑linear loads draw inrush currents and harmonics that add heat beyond the simple full‑load figure. Generator feeders serving large motors often warrant an extra margin.

05

Copper vs. Aluminum

Copper carries more current per cross‑section and terminates more reliably. Aluminum is lighter and cheaper but needs a larger size for the same voltage drop and requires careful termination.

06

Conductor Length

Long runs increase voltage drop. Beyond a certain distance, the voltage‑drop requirement, not ampacity, dictates a larger cable. A cable that works for 20 m may be undersized at 100 m.

Common Errors

Common Generator Cable Sizing Mistakes

Most sizing problems come from a small number of recurring assumptions. Avoiding these errors helps prevent both undersized conductors and unnecessary overspending.

01

Ignoring Voltage Drop

Ampacity is not the only constraint. For long cable runs, voltage drop often determines the minimum size. A conductor that works at 20 m may be undersized at 100 m.

02

Forgetting the 125% Safety Margin

Continuous loads require a margin. Sizing exactly to the full‑load current means the conductor operates at its absolute limit and can overheat under normal conditions.

03

Using the Wrong Resistivity

Copper and aluminum have different resistivities. Using copper values for aluminum (or vice versa) produces an incorrect voltage‑drop calculation and the wrong size.

04

Overlooking Environmental Derating

A cable rated in free air at 25 °C carries less current at 40 °C, in conduit, or bundled with other circuits. Apply derating factors before selecting the final size.

05

Sizing Only for the Generator

The cable must also be coordinated with the breaker and the load. A cable that matches the generator's output may still be unprotected if the breaker is incorrectly selected.

Final cable selection should be checked against the complete load schedule, installation conditions, local electrical codes, and the generator's output breaker rating before equipment is ordered.

Let's talk

Get a Generator + Cable Solution That Fits

A correctly sized cable is only half the equation. As a factory‑direct manufacturer, Shandong Huali delivers the complete package — generator set, connection guidance, and engineering support — without the markup of intermediaries. 8 kVA to 4,000 kVA, prime and standby, with Cummins, Perkins, Weichai, and Yuchai engines and Stamford alternators.

Frequently Ask Questions

Get in touch with us
Leave a message
Contact Form Demo