Motor Starting Calculator

Motor Starting Current Calculator

A motor has two currents: the modest one it draws once it is spinning, and the violent one it draws for the first second or two of getting there. The second is the motor starting current — the inrush surge that can be six to eight times the running current on a direct‑on‑line start — and it is the single largest stress a generator will ever see.

FLA · LRA · SkVA
DOL · Star-Delta · Soft Starter · VFD
HP / kW input
Calculate Starting Current
Free motor starting current calculator for generator sizing.
ShanHua Power

Starting Current Reference

Calculate FLA, LRA, and SkVA for any motor — with starting method adjustments built in.

25+ Years experience
8–4,000 kVA generator range
20+ Countries supplied
Starting Current

Starting Current, Inrush, and Locked Rotor Amps Explained

These three names describe the same event, and the confusion around them is why you will find near-identical calculators for each. Starting current is the general term. Inrush current is the same surge, viewed from the supply side. Locked-rotor current (LRA) is the specific, nameplate-rated value you read off the nameplate or derive from the code letter.

Starting Current The Event

The general term for the elevated current a motor draws while it accelerates from standstill to running speed. It is the event itself — the surge that occurs during startup.

Inrush Current The Demand

The same surge, viewed from the supply side — it is what the generator, transformer, and cables momentarily have to deliver. Inrush is the demand on the supply system.

Locked Rotor (LRA) The Rated Value

The specific, nameplate-rated value of that surge — the current the motor would draw if the rotor were held stationary and full voltage applied. LRA is the rated value you read off the nameplate.

Why kVA Matters More Than kW

All three are typically 5 to 8 times the full-load current, and the number is dominated by the motor's winding impedance. The starting power factor is low — around 0.15 to 0.30 — and the resulting kVA is even higher than the current alone suggests. This is why a motor's starting kW can look modest while its starting kVA is enormous. You size the generator on the kVA, not the kW.

Key Takeaways

Three Terms, One Surge

01
All Three Are the Same Event

Starting current, inrush, and locked rotor describe the same surge from different perspectives. The terms are often used interchangeably — but each has a specific meaning on a nameplate.

02
5–8× Full-Load Current

The starting surge is typically 5 to 8 times the motor's full-load current. This is the number that stresses the generator, cables, and protection devices.

03
Low Starting Power Factor

At startup, the power factor drops to 0.15–0.30, making the starting kVA much larger than the starting kW. This is why generators are sized on kVA, not kW.

04
LRA Comes From the Nameplate

The locked-rotor current is the rated value on the motor nameplate — either direct or derived from the NEMA code letter. Use it for accurate generator sizing.

Starting Current Tool

How the Motor Starting Current Calculator Works

The calculation runs in two steps, each with a different source of truth. Step 1 finds the full-load current (FLA) from rated power, voltage, efficiency, and power factor. Step 2 applies a starting-current multiplier based on the starting method — DOL, Star-Delta, Soft Starter, or VFD.

Step 1 — Find Full-Load Current (FLA)

Enter the motor's horsepower or kilowatts, voltage, efficiency, and power factor. The tool returns the full-load current (FLA) in amps. Then choose a starting method to see the inrush surge.

Enter horsepower (HP) — the tool converts to kW
Line-to-line voltage (V)
Typical: 0.80–0.95
Default: 0.8 for motors
Multiplier applied to full-load current

Step 2 — NEMA Code Letter Method

Enter the motor's horsepower and NEMA code letter from the nameplate. The tool returns the locked-rotor current (LRA) and starting kVA directly from the code letter value.

Select the code letter from the motor nameplate
Starting Methods

Starting Methods Compared: DOL, Star-Delta, Soft Starter, VFD

The starting method is a decision, not a detail — and it changes the current, the torque, and the generator size all at once. The table below uses a 30 kW, 380 V motor drawing 58.3 A full‑load as the reference.

Starting Method Current Multiplier Starting Current Approx. Starting Torque Effect on Generator Size Best For
DOL
Direct-on-Line
6–8× ~350–466 A 100% Largest generator High breakaway torque
Star-Delta
Wye-Delta
2–3× (≈⅓ of DOL) ~117–175 A ~33% 1–2 sizes smaller Centrifugal loads
Autotransformer
65% Tap
~2.5–3.5× ~146–204 A ~42% Reduced by tap² Better torque than star-delta
Soft Starter
Ramped Voltage
2–4× (adjustable) ~117–233 A 25–100% (adjustable) Smallest practical set Retrofit, marginal existing sets
VFD
Variable Frequency Drive
1–1.5× ~58–87 A 100% (any speed) Smallest generator Lowest inrush, variable speed
Key takeaway: The method is often a cheaper way to "shrink" the generator than buying a bigger set. A star-delta or soft start cuts the surge to a third or less, which can drop the required generator by a full size step — the savings in the generator often pays for the starter.

Torque cost: Every reduction has a torque cost. A star-delta start delivers a third of the torque, and a soft starter reduces torque with the square of the voltage. High-inertia loads (crushers, large fans) may not tolerate that — which is why the method and the generator are decided together.
NEMA Code Reference

NEMA Code Letters — Reading Locked Rotor kVA from the Nameplate

For North American motors, the nameplate's code letter (A through V) encodes the locked‑rotor kVA per horsepower, per NEC Table 430.7(B). From it you get the starting current without guessing the multiplier. Most standard three‑phase induction motors are Code F, G, or H (5.0–7.1 kVA/hp).

A–E

Low kVA/HP Range

A: 0–3.14  |  B: 3.15–3.54  |  C: 3.55–3.99  |  D: 4.0–4.49  |  E: 4.5–4.99

These code letters indicate lower locked‑rotor kVA per horsepower. Found on high‑efficiency or specialty motors with reduced inrush.

F–K

Standard Range — Most Common

F: 5.0–5.59  |  G: 5.6–6.29  |  H: 6.3–7.09  |  J: 7.1–7.99  |  K: 8.0–8.99

Most standard three‑phase induction motors fall in F, G, or H. This is the range you will see on most industrial motors.

L–P

High kVA/HP Range

L: 9.0–9.99  |  M: 10.0–11.19  |  N: 11.2–12.49  |  P: 12.5–13.99

Higher kVA per horsepower means higher starting current for the same motor size. Common on motors with higher locked‑rotor torque or lower impedance.

R–V

Very High & Special

R: 14.0–15.99  |  S: 16.0–17.99  |  T: 18.0–19.99  |  U: 20.0–22.39  |  V: 22.4 and above

These are specialty motors with very high inrush — often encountered on high‑torque, high‑inertia loads like crushers and large compressors.

FORMULA

Starting kVA & Locked‑Rotor Current

Starting kVA = kVA/hp × hp
ILR = SkVA × 1000 ÷ (√3 × V)

A 50 hp, 460 V, Code G motor (up to 6.29 kVA/hp) draws 314.5 kVA and 395 A locked‑rotor. Always read the letter — never assume the multiplier.

Quick Reference

Most Standard Motors: Code F, G, or H

5.0–7.1 kVA/hp — the range for most standard three‑phase induction motors. A 50 hp Code G motor starts at 314.5 kVA. The same motor at Code H would draw more — which is why you read the letter rather than assume the multiplier.

Calculation Method

From Code Letter to SkVA and Locked‑Rotor Current

The NEMA code letter gives you the locked‑rotor kVA per horsepower. From that single nameplate value, you can calculate both the starting kVA and the locked‑rotor current for any motor — without guessing the starting‑current multiplier.

01

Step 1 — Find kVA/HP

Locate the motor's code letter on the nameplate. Use the NEC Table 430.7(B) to find the corresponding kVA per horsepower range. For Code G, the range is 5.6–6.29 kVA/hp.

02

Step 2 — Calculate SkVA

SkVA = kVA/hp × hp
For a 50 hp motor with Code G (6.29 kVA/hp):
SkVA = 6.29 × 50 = 314.5 kVA.
This is the apparent power the generator must deliver during startup.

03

Step 3 — Calculate Locked‑Rotor Current

ILR = SkVA × 1000 ÷ (√3 × V)
At 460 V: ILR = 314,500 ÷ (1.732 × 460) = 395 A.
This is the starting current the generator, cables, and breakers must handle.

04

Which Code Letter Is Most Common?

Most standard three‑phase induction motors are Code F, G, or H (5.0–7.1 kVA/hp). Code G is the most common mid‑band estimate for Design B motors. Always confirm the actual letter on the nameplate before calculating.

05

Same Motor, Different Code

A 50 hp Code G motor draws 314.5 kVA at start. The same motor at Code H (7.09 kVA/hp) draws 354.5 kVA13% more. This is why you must read the letter, not assume a generic multiplier.

06

Why SkVA Matters More Than Amps

The starting kVA is what sizes the generator, not the amps alone. A 50 hp Code G motor requires 315 kVA of generator transient capability. The amp value (395 A) is used for cables and breakers — but the generator is sized on kVA.

Worked Examples

Motor Starting Current — Worked Examples

Four examples, calculated with the formulas above, to show the shape of the answer. Each demonstrates the starting current and SkVA for a different motor scenario.

01

30 kW · 380 V · 92% η · 0.85 PF

FLA = 30,000 ÷ (1.732 × 380 × 0.92 × 0.85) = 58.3 A
DOL (6×): 350 A  |  Star-Delta (2×): 117 A
Soft Starter (3×): 175 A  |  VFD (1.2×): 70 A
The method-comparison reference.

02

100 hp · 460 V · Code H

SkVA = 7.10 × 100 = 710 kVA
ILR = 710,000 ÷ (1.732 × 460) = 891 A
A large industrial motor — the locked‑rotor current is near 900 A.

03

50 hp · 460 V · Code G

SkVA = 6.29 × 50 = 314.5 kVA
ILR = 314,500 ÷ (1.732 × 460) = 395 A
The code-letter reference — 395 A locked‑rotor.

04

150 hp · 460 V · Code G

At 5.6 kVA/hp: SkVA = 840, ILR = 1,054 A
At 6.29 kVA/hp: SkVA = 944, ILR = 1,184 A
A big pump or crusher motor — starting kVA of roughly 840–945 kVA.

05

The Consistent Lesson

The starting current is an order of magnitude larger than the running current, and it is the kVA — not the amps — that sizes the generator. The exact generator for that SkVA, and the voltage dip it produces, is covered on the companion motor starting generator sizing calculator.

Final motor starting verification should be checked against the motor's nameplate code letter, the generator's transient capability, and the acceptable voltage dip. The exact generator for the SkVA you calculate here is covered on our companion motor starting generator sizing calculator.

Let's talk

Get the Starting Current Right — and the Generator That Rides It Out

Use the motor starting current calculator above, then feed the starting kVA into our motor starting generator sizing calculator to find the generator and the voltage dip, and convert the running load with our generator hp to kVA calculator.

Frequently Ask Questions

Get in touch with us
Leave a message
Contact Form Demo