Motor Starting Calculator

Motor Starting Generator Sizing Calculator

An electric motor draws four to eight times its running current at locked rotor, and that surge — not the steady-state load — is usually what decides the generator size. Enter the motor's horsepower, NEMA code letter, and starting method — the tool returns the starting kVA (SkVA), the required generator kVA, and the expected voltage dip.

Starting kVA (SkVA)
NEMA code letter
Voltage dip estimate
Calculate Motor Starting Size
Free sizing tool for motor-driven equipment.
ShanHua Power

Motor Starting Reference

Diesel generator sets sized for high-inrush motor loads and demanding start conditions.

25+ Years experience
8–4,000 kVA generator range
20+ Countries supplied
Motor Starting Calculator

How the Motor Starting Generator Sizing Calculator Works

The calculator answers one question: how much apparent power (kVA) must the generator deliver, for the first few seconds, to bring the motor up to speed? It builds the answer in three steps.

Step 1 Find Locked‑Rotor kVA

A motor's starting kVA (SkVA) comes from the nameplate starting current: SkVA = √3 × V × starting amps ÷ 1000, or from the NEMA code letter: SkVA = HP × locked‑rotor kVA per HP.

Step 2 Apply Starting Method

Direct‑on‑line (DOL) draws the full inrush; star‑delta reduces it by a third; a soft starter or VFD reduces it further. The calculator multiplies the SkVA according to the selected method.

Step 3 Check Transient Capability

The alternator must deliver that SkVA while holding the voltage dip within your limit. The tool compares your SkVA against published transient ratings and returns the required generator kVA.

Multiple Motors — The Plant‑Room Rule

For multiple motors, the calculator sums the largest motor's SkVA plus the running kVA of everything else — because only the largest motor starts at a time. This is the standard plant‑room rule, and it prevents oversizing the generator to an unrealistic all‑motors‑starting condition.

What You Get

Starting kVA, Generator Size & Voltage Dip

01
Motor Starting kVA (SkVA)

The locked‑rotor apparent power the motor draws during the first few seconds of startup — the value that determines the generator's transient burden.

02
Required Generator kVA

The generator capacity needed to start the motor while keeping the voltage dip within your acceptable limit — typically 10–15% for most industrial applications.

03
Expected Voltage Dip

The temporary voltage drop at the generator terminals during start. Helps identify whether contactors will drop out or sensitive equipment will be affected.

04
NEMA Code Letter Support

Enter the code letter from the motor nameplate — the calculator uses it to estimate locked‑rotor kVA per horsepower when starting current data is not available.

Motor Starting Tool

How to Size a Generator for Motor Starting

The calculator follows this sequence — Step 1: Find the SkVA from NEMA code or nameplate current. Step 2: Adjust for starting method (DOL, Star-Delta, Soft Starter, VFD). Step 3: Size for the alternator's transient capability.

Motor Starting — NEMA Code Method

Enter the motor horsepower and NEMA code letter from the nameplate. The calculator estimates locked-rotor kVA using the code letter range.

Enter the motor's rated horsepower
Select the code letter from the motor nameplate
Line-to-line voltage (V)
Current multiplier relative to DOL
Maximum acceptable voltage dip at generator terminals

Motor Starting — Nameplate Current Method

Enter the motor's nameplate starting current directly. Use this method when the NEMA code is not available.

Locked-rotor current from nameplate or measurement
Line-to-line voltage (V)
Current multiplier relative to DOL
Maximum acceptable voltage dip at generator terminals
For multiple motors, only the largest starting event matters
Motor Starting Reference

What Is Locked Rotor kVA (SkVA)?

Locked-rotor kVA — usually written SkVA — is the apparent power a motor demands at the instant it is energized, while the rotor is still stationary. It is the number that determines whether a generator can start the motor, because it is far larger than the motor's running kVA.

NEMA Code Letter SkVA per HP NEMA Code Letter SkVA per HP
A 0–3.15 L 9.0–10.0
B 3.15–3.55 M 10.0–11.2
C 3.55–4.0 N 11.2–12.5
D 4.0–4.5 P 12.5–14.0
E 4.5–5.0 R 14.0–16.0
F 5.0–5.6 S 16.0–18.0
G 5.6–6.3 T 18.0–20.0
H 6.3–7.1 U 20.0–22.4
J 7.1–8.0 V 22.4+
K 8.0–9.0
How to use: A 20 HP motor with Code H (6.3–7.1 kVA per HP) draws roughly 126–142 SkVA at start. A 100 HP Code G motor draws about 600 SkVA. That is the number that drives the generator decision.
Starting Methods

Starting Current by Method: DOL, Star-Delta, Soft Starter & VFD

How the motor is started changes everything, because it changes the inrush current — and therefore the SkVA — the generator must absorb. The gentler the start, the smaller the generator.

DOL

Direct-on-Line (DOL)

Starting current: 6–8× full-load current
Generator sizing: 2.5–4× motor kW
DOL applies full voltage immediately and creates the highest surge. Best for smaller motors where full breakaway torque is required and a larger generator is acceptable.

STAR-DELTA

Star-Delta (Wye-Delta)

Starting current: 2.5–3× full-load current
Generator sizing: 1.5–2.5× motor kW
Star-delta roughly halves the starting current and torque. Often suitable for fans, pumps, and centrifugal loads that do not need full torque at zero speed.

SOFT STARTER

Soft Starter

Starting current: 3–4× full-load current
Generator sizing: 1.25–1.75× motor kW
Soft starter provides 30–70% current reduction with a gentle ramp. Particularly useful for retrofit projects where an existing generator is already installed and motor starting remains marginal.

VFD

Variable Frequency Drive

Starting current: 1.1–1.5× full-load current
Generator sizing: 1.1–1.3× motor kW
VFD provides 80–95% inrush reduction with near-unity power factor. The smallest generator, but the harmonic load can still force a larger alternator configuration.

PATTERN

Gentler Start = Smaller Generator

The pattern is simple: the gentler the start, the smaller the generator. But there is a trade-off — reduced-voltage starting also reduces starting torque, which matters if the motor starts under load. Always match the starting method to the load torque profile.

Rule of Thumb

Generator Sizing × Motor kW

DOL: 2.5–4×  |  Star-Delta: 1.5–2.5×  |  Soft Starter: 1.25–1.75×  |  VFD: 1.1–1.3×

A 100 HP pump motor on DOL may need a 300 kW generator. The same motor on a soft starter can often run from a 175 kW set. Starting method is the strongest lever available.

Voltage Dip

Voltage Dip & Alternator Transient Capability

When a motor starts, the generator voltage sags before the governor and excitation recover. How much sag is acceptable depends on what else is connected. The alternator's transient capability determines whether the motor will start cleanly.

01

Voltage Dip Thresholds

30% is a common planning figure for general loads. Motor contactors may drop out below 65% voltage — a real failure if the dip is too deep. Starting kVA falls roughly with the square of the dip — a 30% dip cuts starting kVA to about half (0.7 × 0.7).

02

Subtransient Reactance (X″d)

The alternator's subtransient reactance (X″d) sets how much the voltage dips for a given SkVA. Lower reactance means a stiffer source — better tolerance of motor starting surges and harmonic currents.

03

PMG & AREP Excitation

A low-reactance alternator with PMG (permanent-magnet generator) or AREP excitation — both fitted across the Huali range — recovers faster and holds a shallower dip. PMG feeds the AVR independently, providing stable excitation even under severe voltage dips.

04

Stamford-Alternator Sets

Reference points at 20% voltage dip: 400 kW → ~765 SkVA  |  800 kW → ~2,000 SkVA  |  1,000 kW → ~2,525 SkVA.
The calculator compares your SkVA against these figures, so the "will it start" answer is based on a real alternator.

05

SkVA vs. Generator Rating

A 400 kW generator can deliver nearly twice its continuous rating for a few seconds — about 765 SkVA at 20% dip. This transient overload capability is what allows a generator to start motors that are much larger than its steady-state rating would suggest.

06

Torque Collapse

A reduced-voltage start that saves inrush kVA also cuts starting torque. If a loaded pump or compressor never reaches speed, the cause is usually torque collapse — not generator size. Always confirm the motor's breakaway torque against the reduced-voltage starting torque.

Troubleshooting

Why Won't My Motor Start on a Generator?

When a motor fails to start on a generator, the cause is almost always one of four things. Every one is a design problem you can catch before ordering — by running the SkVA and voltage-dip calculation.

01

Undersized Alternator

The generator's transient kVA is below the motor's SkVA, so the voltage collapses before the motor reaches speed. The fix: increase generator size, choose a lower-reactance alternator, or use a reduced-current starting method.

02

Contactor Dropout

The starting dip pushes voltage below the contactor's hold-in threshold (around 65%), and the starter drops out mid-start. Solutions: use a softer start, increase the generator, or specify contactors with a wider voltage tolerance.

03

AVR Interaction

The voltage regulator's response clashes with the inrush, causing hunting or a stall before the governor catches up. PMG excitation and properly tuned AVR settings are the proven fix for this persistent issue.

04

Torque Collapse

A reduced-voltage start that saves inrush kVA also cuts starting torque, so a loaded pump or compressor never reaches speed. The fix: confirm breakaway torque, use a higher-torque starting method, or unload the motor before start.

05

Catch It Before Ordering

Every one of these is a design problem you can catch before ordering — by running the SkVA and voltage-dip calculation, then matching the motor to the right alternator and excitation. Use the calculator to confirm the match before you buy.

Final motor-starting verification should be checked against the motor's nameplate data, the generator's transient capability curve, the starting method, and the acceptable voltage dip for connected equipment. Our motor starting generator sizing calculator runs these checks automatically.

Let's talk

Get the Right Generator for the Motors That Matter

We build diesel generator sets from 8 kVA to 4000 kVA around Stamford alternators — the brand whose own application notes define motor-starting practice — with PMG and AREP excitationand electronic governors that hold voltage steady under inrush.

Frequently Ask Questions

Get in touch with us
Leave a message
Contact Form Demo