NEC vs IEC Wire Sizing – AWG to mm² Converter
Wire Size Converter

NEC vs IEC Wire Sizing: AWG vs mm² Explained

Shandong Huali Electromechanical Co., Ltd. manufactures diesel generator sets from 8 to 4,000 kVA and exports to more than 20 countries, which puts us on both sides of this divide. We size cable to NEC for our North American customers and to IEC for everyone else, and this guide is built from that same cross‑market experience. For the actual sizing, use our wire size calculator, which handles both AWG and mm².

AWG to mm² conversion
Approximate ampacity
NEC & IEC standards
Convert Wire Size
Free tool for global specifiers and engineers.
Shandong Huali

Global Power & Generator Solutions

We manufacture diesel generator sets from 8 to 4,000 kVA and export to 20+ countries — sizing cable to NEC for North America and IEC for the rest of the world.

8–4,000 kVA generator range
25+ Years experience
20+ Countries supplied
NEC vs IEC Wire Sizing Standards – What's the Difference
Wire Sizing Standards

What Are NEC and IEC Wire Sizing Standards?

NEC and IEC are the two dominant frameworks for sizing electrical conductors, and they serve the same job with different rulebooks.

NEC North American Standard

The National Electrical Code, published by NFPA as standard 70, governs electrical installations across North America. Wire and cable sizing lives in Article 310, where Table 310.16 lists ampacity by conductor size and insulation temperature. Conductors are measured in American Wire Gauge (AWG), which runs backward: a smaller number means a thicker wire. Above 4/0 AWG, sizes are given in thousands of circular mils, kcmil.

IEC International Standard

The International Electrotechnical Commission governs through IEC 60364, the standard for low-voltage electrical installations. Part 5-52 sets current-carrying capacity, and conductors are measured in square millimetres (mm²) of cross-sectional area. Many countries adopt IEC 60364 directly or as a national derivative: BS 7671 in the UK, AS/NZS 3008 in Australia and New Zealand, and GB standards in China.

Common Physics Same Engineering

Underneath the different units and tables, both systems rest on the same thermal physics. A conductor heats up under load, and its rating is the current that holds it below the insulation's temperature limit in a given installation. The Neher-McGrath equations and IEC 60287 calculations that produce the tables are the same engineering either way. The divergence comes from how each code packages those results.

Two Standards, One Physics

Both systems rest on the same thermal physics. A conductor heats up under load, and its rating is the current that holds it below the insulation's temperature limit in a given installation. The Neher-McGrath equations and IEC 60287 calculations that produce the tables are the same engineering either way. The divergence comes from how each code packages those results — AWG vs mm², 75°C vs 70°C columns, and different installation correction factors.

Key Takeaways

Know Your Standard

01
NEC = North America

Uses AWG (backward gauge) and kcmil for larger sizes. Article 310 Table 310.16 is the primary ampacity reference.

02
IEC = Rest of the World

Uses mm² cross-sectional area. IEC 60364 Part 5-52 sets the current-carrying capacity tables for most countries outside North America.

03
Same Physics, Different Packaging

Both systems are built on Neher-McGrath and IEC 60287 thermal equations. The standards diverge in units, temperature columns, and correction factors.

04
Always Specify the Standard

A "14 AWG" conductor and a "2.08 mm²" conductor are the same size — but the ampacity values differ by code. Always specify which standard you are sizing to.

Conductor Units – AWG vs mm² Crosswalk
Conductor Units

Conductor Units: AWG vs mm²

The first practical difference is the unit of measurement, and the table below is the crosswalk between the two.

AWG to mm² Crosswalk & Typical 60°C Ampacity
AWG Cross-Section Typical 60°C Ampacity
14 AWG2.08 mm²15 A
12 AWG3.31 mm²20 A
10 AWG5.26 mm²30 A
8 AWG8.37 mm²40 A
6 AWG13.30 mm²55 A
4 AWG21.15 mm²70 A
2 AWG33.62 mm²95 A
1/0 AWG53.49 mm²125 A
4/0 AWG107.2 mm²195 A

The Crosswalk Is Approximate — That Matters

You do not substitute a 6 AWG cable for a 13.3 mm² cable directly, because the metric world has no 13.3 mm² conductor. The IEC standard series runs 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, and 300 mm² and up.

A 6 AWG cable therefore maps to the nearest standard size, which is 16 mm², not to a notional 13.3 mm² value.

The rule is: convert the size, then select the nearest standard conductor in the target system, then confirm ampacity against that system's own table. The crosswalk gets you close; the ampacity table closes the gap.

Key Takeaways

How to Crosswalk AWG to mm²

01
Convert, Then Select Standard

AWG converts to a theoretical mm² value. Select the nearest standard IEC size — 6 AWG ≈ 13.3 mm² → use 16 mm².

02
IEC Standard Series

1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300 mm² — these are the actual conductor sizes available in metric markets.

03
Crosswalk ≠ Direct Substitution

A theoretical 13.3 mm² conductor does not exist. Always confirm ampacity against the target system's own table.

04
Ampacity Closes the Gap

The crosswalk gets you close; the ampacity table closes the gap. Always verify with the standard you are sizing to.

NEC vs IEC – Key Differences in Wire Sizing
Standards Comparison

Key Differences at a Glance

The table below summarizes where NEC and IEC wire sizing diverge.

Aspect NEC (NFPA 70) IEC (IEC 60364-5-52)
Conductor unitAWG / kcmilmm²
Ampacity sourceTable 310.16Installation-method tables (B.52.x)
Temperature basis60 / 75 / 90°C columns70°C PVC / 90°C XLPE
Continuous load125% rule (NEC 210.19)No continuous-load rule
Grouping deratingFixed factors (1–3 = 1.00, 4–6 = 0.80)Annex B tables by method
Voltage drop3% branch / 5% total (recommended)~3% / 4–5% (clause 525)
Cable tray fillMore permissiveMore conservative
Next-size-up OCPDAllowedNot allowed
The 125% continuous-load rule is the difference most engineers trip on. NEC 210.19 and 210.20 require that a conductor and its overcurrent device be sized at 125% of a continuous load, one that runs three hours or more. A 40 A motor feeder is sized for 50 A. IEC 60364 has no equivalent rule; its ampacity is defined as a cable property for prolonged normal service, with correction factors applied only for installation conditions such as temperature and grouping. The 125% concept in IEC practice applies to the protective device, not the conductor.

Grouping derating also diverges. NEC uses a short table of adjustment factors, from 1.00 for three conductors down to 0.50 for ten to twenty. IEC 60364-5-52 uses more granular Annex B tables keyed to specific methods and tray layouts. And in cable trays the two are far apart: NEC Article 392 allows many more conductors per tray than IEC, which typically caps a run at around six cables with a derating near 0.82.
NEC vs IEC – One Load, Two Standards
Side‑by‑Side Comparison

Worked Example: One Load, Two Standards

The same load, sized under both standards, shows where the systems agree and where they part.

Worked Example

100 A, Three‑Phase, 50 m Run — NEC vs IEC

Take a 100 amp, three‑phase, 50 metre run of PVC‑insulated copper in conduit at 30°C ambient. Under IEC 60364-5-52, Reference Method B selects a 35 mm² conductor rated 110 A at 70°C. Under NEC Table 310.16, the design lands on 2 AWG, about 33.6 mm², rated 115 A at 75°C. The two answers are physically almost identical.

The convergence makes sense: a simple indoor conduit run at standard temperature is where the two standards are closest. They diverge in the harder cases. Add a buried run and IEC brings detailed correction tables for burial depth, ground temperature, and soil resistivity, while NEC points to a separate underground table. Load several cables into a tray and NEC allows more conductors per tray than IEC will accept. Run a continuous load and NEC adds the 125% factor while IEC does not.

The lesson is not that one standard is right. It is that the standards agree on the fundamentals and differ on the margins, and the margins are where real installations live.

Market Reference

Which Standard Applies to Your Market?

The decision between NEC and IEC is rarely a choice; it is set by where the equipment will be installed.

01

United States, Canada, Mexico

NEC (NFPA 70) — the North American standard for electrical installations.

02

United Kingdom

BS 7671 — the UK national standard, derived from IEC 60364.

03

Europe

IEC 60364 or national derivatives (e.g., VDE in Germany, NF C 15-100 in France).

04

Middle East, Asia, Africa

IEC 60364 or national derivatives, with local variations in voltage and frequency.

05

Australia, New Zealand

AS/NZS 3008 — the IEC‑derived standard for cable sizing in the region.

06

China

GB standards — IEC‑aligned national standards for electrical installations.

For a manufacturer, this is where the standards question becomes a business question. The same generator set shipped to two customers needs two feeder‑cable specifications, one in AWG for North America and one in mm² for most of the rest of the world. The conductor that is correct under NEC is not automatically the conductor you specify under IEC, even though the underlying physics is identical.

Generator Feeders

From Wire Sizing to Generator Cable Sizing

Of all the conductors in a power system, the generator feeder is the one where NEC vs IEC wire sizing matters most. It carries continuous load, often a large motor‑starting surge, and it runs between the generator and the switchgear where a sizing error is expensive and hard to fix.

A

Under NEC

A generator feeder is a continuous load under NEC, so the 125% rule applies. It is usually a long run, so voltage drop governs. The 125% factor and voltage drop together often push the conductor size up significantly.

B

Under IEC

Under IEC, the same feeder is sized by installation method with no continuous‑load factor. This is why the same generator can carry a different cable size depending on the destination market. Get this right and the generator delivers its full rating; get it wrong and the cable runs hot or the voltage sags under load.

Once the conductor is specified, the next question is whether the generator itself is sized for the load it feeds. The feeder size and generator capacity must be coordinated — and both depend on the same load data and the same destination standard.

Let's talk

About Shandong Huali

Shandong Huali Electromechanical Co., Ltd. manufactures diesel generator sets, dust-suppression equipment, and industrial automation systems, with over 25 years of experience and exports to more than 20 countries. We size power equipment to both NEC and IEC standards every day, and we publish free electrical reference tools to help engineers and buyers specify power systems correctly.

Frequently Ask Questions

Get in touch with us
Leave a message
Contact Form Demo